6.3 Actuator Settings
This screen displays the current actuator settings. These settings are all relevant to standard actuator
control functions.
6.3.1 Basic Settings
Close Action
The actuator can be configured to close on torque for seating valve types or limit for non-seating valve
types. Limit means the actuator will stop moving once it reaches the set closed travel limit. Torque
means the actuator will stop when it reaches the set closed torque limit (Default 40% of Rated).
Open Action
The actuator can be configured to open on torque for back-seating valve types or limit for non-back-
seating valve types. Limit means the actuator will stop moving once it reaches the set open travel limit.
Torque means the actuator will stop when it reaches the set open torque limit (Default 40% of Rated).
Direction to Close
This sets the direction of rotation for the actuator to perform a close operation to the valve. There are
two available settings; clockwise and anti-clockwise. A close command will always operate in the set
direction; therefore a reversal of controls is not required when changing the operating direction to suit
the valve.