actuator will remain stationary until a request to move in the opposite direction is received or the
obstruction is removed. To set up obstruction settings see section 5.3.3.
5.3.3 Obstruction Values Setup
Backoff Distance (%)
The distance the actuator will back off as a percentage of total travel.
Backoff Time (Sec)
The time in seconds before a back off command is executed.
5.3.4 Manual Test Knob Setup
Manual Test Knob Active
Enables or disables the Manual Test knob option provided it is fitted to the actuator.
5.4 Advanced Settings 2
5.4.1 Travel Alarm Thresholds
Direction Change Threshold Distance (%)
The distance the actuator must move (as a percentage of full travel) before a direction change is
registered by the data logger as a start. The default setting is 0.25%.
Total Direction Changes Threshold (1000s)
This can be used to generate a Travel Alarm when a set number of direction changes have been
performed by the actuator.
Total Travel Distance Threshold (%)
This can be used to generate a Travel Alarm when a set distance has been travelled by the actuator.
5.4.2 Bumpless Transfer Setup
Bumpless Transfer Distance (%)
This is the percentage of position error that will reduce the actuator speed to the Bumpless Transfer
Speed.
Bumpless Transfer Speed (%)
This is the speed that the actuator will revert to if the bumpless transfer distance is exceeded. It is
measured as a percentage of rated maximum speed and the default setting is 40%.