57
6.11 UI Settings
6.11.1 Indication Configuration
Home Screen
There are four different home screen options:
Position: This shows the position of the actuator as a percentage.
Torque Analogue Plus Position: This shows the position of the actuator and an analogue torque meter.
Torque Digital Plus Position: This shows the position of the actuator and a digital torque readout in Nm.
Positioner: This shows a digital and analogue readout of position and demand. Demand will only be
shown when the actuator is controlled by a network or a 4-20mA signal.
Mid Travel LED Function
Shows the current function of the Mid Travel LED, the functions available are:
Disabled: The LED will be off.
Enabled: The LED will be active when the actuator is not at its limits.
Blinker: The yellow lights will blink when the actuator is travelling and will remain on when the actuator
is stopped.
LED Blinks When Alarm present: The yellow lights are on during mid-travel and will blink alternately
when an alarm is present.
LED ON when Alarm present: The yellow lights will only come on blinking alternately when an alarm is
present.
Alarm LED Setting
Shows the current setting for the Alarm LED.
No Alarms Indicated: The yellow lights will not indicate an active alarm.
Active on any Alarm: The LED will be active when an actuator or valve alarm is present if the
appropriate option is set above.
Active on any Service alarm: The LED will be active when a Service alarm is present if the appropriate
option is set. A service alarm indicates the actuator requires service, due to set duty parameters being
met.
Active on any Service or Alarm: The yellow lights indicate active alarms and active service alarms if the
appropriate option is set above. A service alarm indicates the actuator requires service due to set duty
parameters being met.
Close Limit LED Colour
The colour of the close limit LED can be set, either red or green. The open limit LED will be the inverse of
the close limit setting.
Summary of Contents for Insight 2