79
8.2 Contact Relays
8.2.1 Contact – Function
This setting determines the function of the selected relay contact. The drop down box enables the user
to select from the following function settings.
Condition
Description
Closed Limit
The actuator has reached its closed limit
Open Limit
The actuator has reached its open limit
Fault Alarm
The actuator has detected a fault and is displaying an actuator alarm
Position % Open
The actuator has reached a user defined position
Motor Running
The motor is running
Closing
The actuator is moving closed
Opening
The actuator is moving open
Moving
The actuator is moving in either direction
Stall (Mid-Travel)
The motor has stalled whilst away from the limits
Stall (Any Position)
The motor has stalled whilst at either limit
Over Pressure (Mid-Travel)
The motor has stalled at any position
Over Pressure (End of Travel)
Active when an over pressure is present at either limit
Over Pressure (Any Position)
Active when an over pressure is present at any position of travel
Stop Selected
The Local/Stop/Remote switch is switched to stop
Local Selected
The Local/Stop/Remote switch is switched to Local
Remote Selected
The Local/Stop/Remote switch is switched to Remote
Control Alarm
The actuator is portraying a control alarm
ESD Active
The actuator is performing its ESD Function
Temperature (
⁰C)
The actuator has reached a set Temperature
Manual Override Switch
Manual override is active
Accumulator Pressure Switch
Accumulator pressure has been exceeded
External Manual Reset Switch
External manual reset switch is active
Motor Thermostat Switch
Motor thermostat is active
Partial Stroke Passed
The actuator has passed its partial stroke test
Partial Stroke Failed
The actuator has failed its partial stroke test
Monitor Output
The actuator is available for remote operation
None
The relay is disabled
8.2.2 Contact – Value
This is directly related to some of the relay functions shown above. The setting is configurable from 0%
to 100% in increments of 0.1%.
8.2.3 Contact – Form
Set the relay contact type to normally open (make on active) or normally closed (break on active).