56
6.10.2 Position Settings
Min Span Position (%)
This setting can restrict the minimum allowable travel position without adjusting the set limits.
Max Span Position (%)
This setting can restrict the maximum allowable travel position without adjusting the set limits.
Deadband (%)
Shows the Deadband setting for the actuator. Refer to the IQ3 Full Configuration Manual for Details.
Hysteresis Band (%)
Shows the Hysteresis Band setting for the actuator. Refer to the IQ3 Full Configuration Manual for
Details.
Motion Inhibit Time (Sec)
This is the amount of time the actuator will not respond to a control signal after moving to a new
position. This is configurable from 0 – 1000 seconds.
6.10.3 Interrupter Timer
Interrupter Timer Enable
For indication only, shows whether the interrupter timer is enabled or disabled.
Interrupter Timer Close Position (%)
This is the position the interrupter timer will activate when running in the closed direction. Setting this
to 0% will result in non-interrupted travel.
Interrupter Timer Open Position (%)
This is the position the interrupter timer will activate when running in the open direction. Setting this to
100% will result in non-interrupted travel.
Interrupter Timer On Time (sec)
The time the interrupter timer will be active for before turning off. This is the pause length while the
interrupter timer acting on a movement.
Interrupter Timer Off Time (sec)
The time the interrupter timer will be inactive for before turning on. This is the period of movement
between each interruption.
Summary of Contents for Insight 2
Page 1: ......