48
6.4.4 Torque Profile Settings
Torque Profile Open
Allows the plotting of the torque profile in the open direction to be enabled or disabled.
Torque Profile Close
Allows the plotting of the torque profile in the close direction to be enabled or disabled.
6.5 Power Settings
This menu displays power settings relating to the actuator type and battery.
6.5.1 Power Type
Power Type
For indication only, shows the power type of the actuator. The power type options are:
Three Phase Standard: For three phase supply actuators which are not built to modulating specification.
Single Phase: For single phase supply actuators.
DC: For direct current supply actuators.
Three Phase Modulating: For three phase supply actuators which are built to a modulating
specification.
Solid State Starter Brake
The Solid State Starter brake injects a DC voltage into the motor in order to slow the magnetising of the
fields and bring the motor to a halt. In this setting, the option for the Solid State Starter brake is viewed
and set, only available for actuators with a Solid State Starter fitted. The options available are;
Brake Off: The Solid State Starter brake is off.
Brake Open: The brake is active in the open direction only.
Brake Close: The brake is active in the close direction only.
Brake Open and Close: The brake is active in both the open and close direction.
Modulating Actuator
For indication only, shows whether the actuator is built for Isolating or Modulating duty.
Summary of Contents for Insight 2