Fault messages, causes and remedies
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
39
7
Fault messages, causes and remedies
Pos: 35 /Doppelblech/Geräte/R1002/9 Fehlermeldungen/Fehlertabelle AI100 @ 0\mod_1184851156984_501.doc @ 4155 @
Message Meaning
Cause / Remedy
Error 1
Value for Teach-In is not plausible
(measurement value is smaller than 25
or larger than 960)
Sensor has no contact with the sheet
Sensor cable is cut off
Sensor type is not suitable
System might be defective
Error 2
Value for external Teach-In is not
plausible
(measurement value is smaller than 25
or larger than 960)
Sensor has no contact with the sheet
Sensor cable is cut off
Sensor type is not suitable
System might be defective
Error 3
External Teach-In is not permitted
(system is still in factory-set condition)
Factory settings have not been
overwritten – perform Teach-In via
operating keys once.