for pairs of sensors
Start-up
B0003308 / 1.4 / 13.02.2013
30
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Pos: 27 /Doppelblech/Geräte/R1002/6 Inbetriebnahme / Bedienung/Einschalten und Hochfahren @ 0\mod_1184848726296_501.doc @ 4120 @
6.3 Switching
on
and Powering up
Applying the supply voltage (24 V DC) to the unit will switch the unit on, as soon as power is
supplied the POWER LED lights.
When the operation system is loaded, the manufacturer and system information will be shown for a
short period.:
Roland
Electronic GmbH
and then
A100
(I100 for system I100)
Sw.1.0 21.05.2007
1
Fig. 19: Indication of manufacturer and system information
The unit changes automatically to the measuring mode and will work with the last taught values.
Pos: 28 /Doppelblech/Geräte/R1002/6 Inbetriebnahme / Bedienung/Betriebszustände @ 0\mod_1185181216687_501.doc @ 4289 @
6.4 Operational
conditions
6.4.1 Undisturbed
operation
As long as no fault is detected in the measuring mode, no operator actions are required.
The unit measures continuously and sets the signal output according to the measurement result.
6.4.2
Detection of 0-sheet, 1-sheet or 2-sheet
As long as the measured value is within the range of 85% to 115% of the nominal value, the
system will detect 1-sheet.
If the measured value is outside the range, the system will then detect 0-sheet (no sheet)
or 2-sheet (double sheet).
• The associated LED (0-SHEET, 1-SHEET, 2-SHEET) will light up accordingly.
• The associated signal output will be set to low resistance (active).
• The signal outputs 0-SHEET, 1-SHEET, 2-SHEET will deliver a switch voltage only if an
external positive voltage (max. +24V, min. 50mA) is applied to the COMMON input (terminal 8).
1