38
Description
Code
Unit
Min.
Max.
Default
Notes
Type of solar thermal
input contact (digital
1)
i1
----
0
1
0
0 = active if contact is closed
1 = active if contact is open
High/low pressure
end compressor
protection
i2
min
0
120
0
Photovoltaic input
enabling (digital 2)
i3
----
0
1
1
0 = input disabled
2 = input enabled
Type of photovoltaic
input contact (digital
2)
i4
----
0
1
0
0 = active if contact closed
1 = active if contact open
Number of digital
input alarms per
equipment block
i8
----
0
15
0
Time for digital input
alarm counter reset
i9
min
1
999
240
Buzzer enabling
u9
----
0
1
1
0 = buzzer disabled
1 = buzzer enabled
Switching on time for
Monday
Hd1
----
1
2
1
1 = HOn1-HOF1
2 = HOn2-HOF2
Switching on time for
Tuesday
Hd2
----
1
2
1
1 = HOn1-HOF1
2 = HOn2-HOF2
Switching on time for
Wednesday
Hd3
----
1
2
1
1 = HOn1-HOF1
2 = HOn2-HOF2
Switching on time for
Thursday
Hd4
----
1
2
1
1 = HOn1-HOF1
2 = HOn2-HOF2
Switching on time for
Friday
Hd5
----
1
2
1
1 = HOn1-HOF1
2 = HOn2-HOF2
Switching on time for
Saturday
Hd6
----
1
2
2
1 = HOn1-HOF1
2 = HOn2-HOF2
Switching on time for
Sunday
Hd7
----
1
2
2
1 = HOn1-HOF1
2 = HOn2-HOF2
Time for first switch
on timeslot
HOn1
----
00:00
23.59
--:--
--:-- = function excluded
Time for first switch
off timeslot
HOF1
----
00:00
23.59
--:--
--:-- = function excluded
Time according to
timeslot switch on
HOn2
----
00:00
23.59
--:--
--:-- = function excluded
Time according to
timeslot switch off
HOF2
----
00:00
23.59
--:--
--:-- = function excluded
Equipment address
LA
----
1
247
247
Baud Rate
Lb
----
0
3
2
0 = 2400
1 = 4800
2 = 9600
3 = 19200