36
Description
Code
Unit
Min.
Max.
Default
Notes
Local display data
P5
----
0
3
0
0 = Upper probe
1 = Operation setpoint
2 = Lower probe
3 = Evaporator probe
Remote display data
P6
----
0
3
0
0 = Upper probe
1 = Operation set-point
2 = Lower probe
3 = Evaporator probe
Display data refresh
time specified in
tenths of a second
P8
1/10 sec
0
250
5
Work set hysteresis
r0
ºC / ºF
0.1
30.0
7.0
Minimum auto cycle
set point
r1
ºC / ºF
10.0
r2
40.0
Maximum auto cycle
set point
r2
ºC / ºF
r1
100.0
70.0
Minimum eco cycle
set point
r3
ºC / ºF
10.0
r4
40.0
Maximum eco cycle
set point
r4
ºC / ºF
r3
100.0
56.0
Work set change lock
r5
----
0
1
0
1 = it is not possible to change the set
point; it can only be seen.
Delay in equipment
start up
C0
min.
0
240
5
Compressor protections
Delay as from last ON
C1
min.
0
240
5
Delay as from last
OFF
C2
min.
0
240
5
Minimum ON time
C3
sec
0
240
0
No. compressor
operating hours req.
for maintenance
C10
hour
0
9999
0
0 = function excluded
Delay air temperature
sample taking for
cold evaporator test
C11
min
0
999
120
Minimum delay
between fan start-up
and compressor ac-
tivation for incoming
air temperature check
C12
min
0
240
1
Timeout solar thermal
cycle
C13
min
0
240
20
Delay for damaged
fan check
C14
min
-1
240
20
-1 = disabled function
Defrosting type
d1
----
0
2
2
0 = with heating element
1 = with hot gas
2 = with compressor stopped
Summary of Contents for Dalis 200DHW4