Functional description of PRxx1 series controllers Rev.H.doc
2016-10-28
28/43
[21]
Locked door mode
The output line is active as long as the controller operates in
Locked Door Mode (see 2.5 Door Modes)
[25]
Pulse upon
disarming
The output line is activated for 2 sec. when the controller
switches to Disarmed Mode (see 2.6 Armed and Disarmed
Modes)
[26]
Pulse upon arming
The output line is activated for 2 sec. when the controller
switches to Armed Mode (see 2.6 Armed and Disarmed
[37]
AC failure
The output line is active if AC power supply failure lasts for
more than 6 minutes. Signaling at the output line is ceased
after approx. 1 minutes from AC power supply recovery. The
function is available in PR411DR controller only
[38]
Low battery
The output line is active if battery voltage drops below 11,7V
for at least 8 minutes. Signaling at the output line is ceased
after approx. 6 minutes from AC power supply recovery. The
function is available in PR411DR controller only
[64]
LIGHT
The output line signals actual state of
LIGHT
flag. The output
is active when flag is on and the output is inactive when flag
is off (see 2.7.9 System Flags)
[65]
Tamper Alarm
The output line signals actual state of
TAMPER
flag. The output
is active when flag is on and the output is inactive when flag
is off
[66]
AUX1
The output line signals actual state of
AUX
1 flag (see 2.7.9
[67]
AUX2
The output line signals actual state of
AUX
1 flag (see 2.7.9
[68]
Intruder Alarm
The output line signals actual state of
INTRUDER
flag (see
[69]
Duress Alarm
The output line signals actual state of
DURESS
flag (see 2.7.9
[70]
Trouble Alarm
The output line signals actual state of
TROUBLE
flag (see 2.7.9
[71]
Entry Delay
The output line is active as long as
ENTRY DELAY
timer is
counting down (see 2.7.9 System Flags)
[72]
Exit Delay
The output line is active as long as
EXIT DELAY
timer is
counting down (see 2.7.9 System Flags)
[73]
Proximity card
present
The output line is active as long as any EM125kHz (UNIQUE)
standard card is present in card holder of PR-621-CH/PR821-
CH controller plus the time specified by means of timer
CARD
PRESENT
–
SWITCH OFF DELAY
. The function is also available in
PR311SE, PR611 and PR621 controllers.
[74]
Antenna switching
on term. ID1 and
ID0
The output enables alternate switching of antenna coils in
controller and external reader. Connection of this output to
the input of external reader improves card reading when
both devices are installed too close on both sides of door.
This output is available only for controllers with built-in