Operating mode of signal lights on boom
N.B.:
to reduce power consumption, the controller automatically sets this par. to
during battery powered operation.
Disabled. Lights always off.
Lights always on.
Lights on with boom stationary, flashing when boom is moving.
Short flash with boom stationary, flashing normally when boom is moving.
Short flash with boom closed, flashing normally when boom is moving, off when boom is open.
Clock contact configuration.
When the clock function is active, the barrier opens and remains open.
At the end of the programmed time set with the external device (clock), the barrier closes.
When the clock function is active, the barrier opens and remains open. Any command signal received is ignored.
When the clock function is active, the barrier opens and remains open. Any command signal received is accepted.
When the barrier returns to the completely open position, the clock function is reactivated.
Enable safeguarded barrier closure
Enabling this parameter ensures that the barrier is not left open due to incorrect and/or accidental commands.
This function is NOT enabled if:
• the barrier receives a STOP command;
• the sensing edge is activated;
• the number of closure attempts set by parameter
$
has been reached.
Disabled. Parameter
is not visible.
Enabled.
If the barrier is closed as a result of a step mode command, after a period of time set with parameter
,
the control unit signals a 5 second warning with the flashing light (regardless of the parameter
$
), and then
the barrier closes.
Safeguarded closure activation time setting
N.B.:
this parameter is not visible if the value of parameter
=
.
Wait time settable from 2 to 90 s.
Wait time settable from 2 to 9 min.
Parking access mode selection
N.B.: If enabled with values
,
or
, photocell activation during a closing manoeuvre will always trigger a
reopening manoeuvre unless parameter
is set. Parameters
$
,
$
,
,
,
and
are not visible.
With
=
,
,
the barrier re-closes after a pause time set at parameter
(if
is set to a value
different from
).
For more information, see chapter 14 “Examples of applications in parking access mode”.
Disabled. Parameter
is not visible.
Bi-directional mode with immediate closure.
When entering and leaving the parking area, the barrier is opened with an
AP
open command. Once the vehicle
has crossed the barrier and released contact
FT
(NC) (e.g. from magnetic loop), the barrier closes immediately.
When parameter
=
, the barrier open and remains open until the vehicle has completed the passage. If
the vehicle moves back, the barrier remains open.
NOTE
: it is possible to add further 5 s delay before closing, setting
$
.
Directional mode 1.
When entering the parking area, the barrier is opened with an AP open command. Once the vehicle has crossed
the barrier and released contacts
FT
(NC) and
PED
(NO), the barrier closes. When leaving the parking area, the
barrier is opened by a
PED
command received from the magnetic loop. Once the vehicle has crossed the barrier
and released contact
FT
(NC), the barrier closes.
When parameter
=
, the barrier open and remains open until the vehicle has completed the passage. If
the vehicle moves back, the barrier remains open.
NOTE
: it is possible to add further 5 s delay before closing, setting
$
.
Directional mode 2.
When entering, the barrier is opened with an
AP
open command, and closes after the automatic closing time
set with parameter
.
NOTE
: in order to have the automatic closing set parameter
different to
.
When leaving the parking area, the barrier is opened by a
PED
command received from the magnetic loop.
Once the vehicle has crossed the barrier and released contact
FT
(NC), the barrier closes.
NOTE
: it is possible to add further 5 s delay before closing, setting
$
.