StepLogicTM, Basic Logic and Timer/Counter Functions
H-3
StepLogic
TM
Using Basic Logic Functions
Digital input and digital output parameters can be configured to use
logic to transition to the next step. Logic In1 and Logic In2 are
defined by programming Digital Inx Sel parameters (A051-A054) to
option 23 “Logic In1” or option 24 “Logic In2”.
Example
•
Run at Step 0.
•
Transition to Step 1 when Logic In1 is true.
Logic senses the edge of Logic In1 when it transitions from off
to on. Logic In1 is not required to remain “on”.
•
Transition to Step 2 when both Logic In1 and Logic In2 are true.
The drive senses the level of both Logic In1 and Logic In2 and
transitions to Step 2 when both are on.
•
Transition to Step 3 when Logic In2 returns to a false or off
state. Inputs are not required to remain in the “on” condition
except under the logic conditions used for the transition from
Step 2 to Step 3.
Time
Logic In1
Logic In2
Frequency
Start
Step 0
Step 1
Step 2
Step 3
Summary of Contents for Reliance Electric MD65
Page 2: ...Instruction Manual MD65 AC Drive User Manual Version 2 0 D2 3519 2 ...
Page 7: ...IV MD60 AC Drive User Manual ...
Page 9: ...VI MD65 AC Drive User Manual ...
Page 11: ...VIII MD65 AC Drive User Manual ...
Page 13: ...1 2 MD65 AC Drive User Manual ...
Page 47: ...6 12 MD65 AC Drive User Manual ...
Page 119: ...10 12 MD65 AC Drive User Manual ...
Page 123: ...A 4 MD65 AC Drive User Manual ...
Page 129: ...B 6 MD65 AC Drive User Manual ...
Page 135: ...C 6 MD65 AC Drive User Manual ...
Page 139: ...D 4 MD60 AC Drive User Manual ...
Page 149: ...Accessories E 10 ...
Page 179: ...PID Set Up I 10 ...
Page 184: ......
Page 185: ......
Page 186: ......