Troubleshooting the Drive
10-9
10.2.4 Problem: Motor Does Not Start
Cause(s)
Indication
Corrective Action
No output voltage to the
motor.
None
Check the power circuit.
•
Check the supply voltage.
•
Check all the fuses and
disconnects.
Check the motor.
•
Verify that the motor is
connected properly.
Check the control input
signals
•
Verify that a Start signal is
present. If 2-Wire control
is used, verify that either
the Run Forward or Run
Reverse signal is active,
but not both.
•
Verify that I/O Terminal 01
is active.
•
Verify that Start Source
(P036) matches your
configuration.
•
Verify that Reverse
Disable (A095) is not
prohibiting movement.
Drive is faulted.
Flashing red
STATUS LED.
Clear fault.
•
Press Stop
•
Cycle power
•
Set Fault Clear (A100) to
1 = Clear Faults.
•
Cycle digital input if Digital
Inx Sel (A051-A054) is set
to 7 = Clear Fault.
Summary of Contents for Reliance Electric MD65
Page 2: ...Instruction Manual MD65 AC Drive User Manual Version 2 0 D2 3519 2 ...
Page 7: ...IV MD60 AC Drive User Manual ...
Page 9: ...VI MD65 AC Drive User Manual ...
Page 11: ...VIII MD65 AC Drive User Manual ...
Page 13: ...1 2 MD65 AC Drive User Manual ...
Page 47: ...6 12 MD65 AC Drive User Manual ...
Page 119: ...10 12 MD65 AC Drive User Manual ...
Page 123: ...A 4 MD65 AC Drive User Manual ...
Page 129: ...B 6 MD65 AC Drive User Manual ...
Page 135: ...C 6 MD65 AC Drive User Manual ...
Page 139: ...D 4 MD60 AC Drive User Manual ...
Page 149: ...Accessories E 10 ...
Page 179: ...PID Set Up I 10 ...
Page 184: ......
Page 185: ......
Page 186: ......