MD65 AC Drive User Manual
9.1
Basic Program Group Parameters
The Basic Program Group contains the most commonly used
parameters to simplify the start-up process.
Set to the motor nameplate rated volts.
Set to the motor nameplate rated frequency.
Set to the maximum allowable motor current. The drive will fault on
an F7 Motor Overload if the value of this parameter is exceeded by
150% for 60 seconds or 200% for 3 sec.
Sets the lowest frequency the drive will output continuously.
Sets the highest frequency the drive will output.
P031 Motor NP Volts
Range:
20 VAC to Drive Rated Volts
Default:
Based on Drive Rating
See also:
d004, A084-A087
P032 Motor NP Hertz
Range:
15 to 400 Hz
Default:
60 Hz
See also:
A084-A087, A090
P033 Motor OL Current
Range:
0.0 to (Drive Rated Amps x 2)
Default:
Based on Drive Rating
See also:
A055, A058, A061, A089, A090, A098, A114, A118
P034 Minimum Freq
Range:
0.0 to 400.0 Hz
Default:
0.0 Hz
See also:
d001, d002, d013, P035, A085-A087, A110, A112
P035
Maximum Freq
Range:
0 to 400 Hz
Default:
60 Hz
See also:
d001, d002, d013, P034, A065, A078, A085-A087,
A111, A113
Summary of Contents for Reliance Electric MD65
Page 2: ...Instruction Manual MD65 AC Drive User Manual Version 2 0 D2 3519 2 ...
Page 7: ...IV MD60 AC Drive User Manual ...
Page 9: ...VI MD65 AC Drive User Manual ...
Page 11: ...VIII MD65 AC Drive User Manual ...
Page 13: ...1 2 MD65 AC Drive User Manual ...
Page 47: ...6 12 MD65 AC Drive User Manual ...
Page 119: ...10 12 MD65 AC Drive User Manual ...
Page 123: ...A 4 MD65 AC Drive User Manual ...
Page 129: ...B 6 MD65 AC Drive User Manual ...
Page 135: ...C 6 MD65 AC Drive User Manual ...
Page 139: ...D 4 MD60 AC Drive User Manual ...
Page 149: ...Accessories E 10 ...
Page 179: ...PID Set Up I 10 ...
Page 184: ......
Page 185: ......
Page 186: ......