MD65 AC Drive User Manual
Sets the serial port rate for the RS485 port.
Important:
Power to the drive must be cycled before any changes
will affect drive operation.
Sets the drive node address for the RS485 port if using a network
connection.
Important:
Power to the drive must be cycled before any changes
will affect drive operation.
Selects the drive’s response to a loss of the communication
connection or excessive communication errors.
0 = Fault (Default): Drive will fault on an F81 Comm Loss and coast
to stop.
1 = Coast Stop: Stops the drive via coast to stop.
2 = Stop: Stops the drive via the setting in Stop Mode (P037).
3 = Continu Last: Drive continues operating at communication
commanded speed saved in RAM.
A103 Comm Data Rate
Range:
0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19.2 K
5 = 38.4 K
Default:
4 = 19.2 K
See also:
d015
A104 Comm Node Addr
Range:
1 to 247
Default:
1
See also:
d015
A105 Comm Loss Action
Range:
0 = Fault
1 = Coast Stop
2 = Stop
3 = Continu Last
Default:
0 = Fault
See also:
d015, P037, A106
Summary of Contents for Reliance Electric MD65
Page 2: ...Instruction Manual MD65 AC Drive User Manual Version 2 0 D2 3519 2 ...
Page 7: ...IV MD60 AC Drive User Manual ...
Page 9: ...VI MD65 AC Drive User Manual ...
Page 11: ...VIII MD65 AC Drive User Manual ...
Page 13: ...1 2 MD65 AC Drive User Manual ...
Page 47: ...6 12 MD65 AC Drive User Manual ...
Page 119: ...10 12 MD65 AC Drive User Manual ...
Page 123: ...A 4 MD65 AC Drive User Manual ...
Page 129: ...B 6 MD65 AC Drive User Manual ...
Page 135: ...C 6 MD65 AC Drive User Manual ...
Page 139: ...D 4 MD60 AC Drive User Manual ...
Page 149: ...Accessories E 10 ...
Page 179: ...PID Set Up I 10 ...
Page 184: ......
Page 185: ......
Page 186: ......