MD65 drives support the RS485 (MDI) protocol to allow efficient
operation with Rockwell Automation peripherals. In addition, some
Modbus functions are supported to allow simple networking. MD65
drives can be multi-dropped on an RS485 network using Modbus
protocol in RTU mode.
For information regarding DeviceNet or other communication
protocols, refer to the appropriate user manual.
Network Wiring
Network wiring consists of a shielded 2-conductor cable that is
daisy-chained from node to node. See figure F.2.
Only pins 4 and 5 on the RJ45 plug should be wired. The other pins
on the MD65 RJ45 socket contain power, etc., for other Rockwell
Automation peripheral devices and must not be connected.
Figure F.1 – Sample Network
Controller
Figure F.2 – Network Wiring Diagram
Master
MD65 Drive
Node 1
4
5
MD65 Drive
Node 2
4
5
MD65 Drive
Node "n"
4
5
TxRxD+
TxRxD-
TxRxD+
TxRxD-
TxRxD+
TxRxD-
NOTE: The shield is connected at ONLY ONE end of each cable segment.
Shield
Shield
Shield
120 ohm resistor
120 ohm resistor
X
X
X
FRONT
PIN 8
PIN 1
Summary of Contents for Reliance Electric MD65
Page 2: ...Instruction Manual MD65 AC Drive User Manual Version 2 0 D2 3519 2 ...
Page 7: ...IV MD60 AC Drive User Manual ...
Page 9: ...VI MD65 AC Drive User Manual ...
Page 11: ...VIII MD65 AC Drive User Manual ...
Page 13: ...1 2 MD65 AC Drive User Manual ...
Page 47: ...6 12 MD65 AC Drive User Manual ...
Page 119: ...10 12 MD65 AC Drive User Manual ...
Page 123: ...A 4 MD65 AC Drive User Manual ...
Page 129: ...B 6 MD65 AC Drive User Manual ...
Page 135: ...C 6 MD65 AC Drive User Manual ...
Page 139: ...D 4 MD60 AC Drive User Manual ...
Page 149: ...Accessories E 10 ...
Page 179: ...PID Set Up I 10 ...
Page 184: ......
Page 185: ......
Page 186: ......