9-6
MD65 AC Drive User Manual
4 = Preset Freq: External frequency command as defined by
Preset Freq x (A070-A077) when Digital Inx Sel (A051-A054) are
programmed as “Preset Frequencies,” and the digital inputs are
active.
5 = Comm Port: External frequency command from the
communications port.
6 = Stp Logic: External frequency command as defined by Preset
Freq x (A070-A077) and Stp Logic x (A140-A147).
7 = Anlg ln Mult: External frequency command as defined by the
product of the analog inputs (shown in Analog ln 0-1-V (d020) and
Analog ln 4-20mA (d021). [Analog ln 0-10V] x [Analog ln 4-20mA] =
Speed Command
Example: 100% x 50% = 50%
Sets the rate of acceleration for all speed increases. See figure 9.1.
Maximum Frequency / Accel Time = Accel Rate
Sets the rate of deceleration for all speed decreases. See figure 9.2.
P039 Accel Time 1
Range:
0.0 to 600.0 sec
Default:
5.0 sec
See also:
P038, P040, A051-A054, A067, A070-A077,
A140-A147
Figure 9.1 – Accel Time 1 (P039)
P040 Decel Time 1
Range:
0.1 to 600.0 sec
Default:
5.0 sec
See also:
P038, P039, A051-A054, A068, A070-A077,
A140-A147
Speed
0
Time
P035 [Maximum Freq]
P039 or A067
[Accel Time x]
P040 or A068
[Decel Time x]
0
Acceleration
D
ecel
era
tion
Summary of Contents for Reliance Electric MD65
Page 2: ...Instruction Manual MD65 AC Drive User Manual Version 2 0 D2 3519 2 ...
Page 7: ...IV MD60 AC Drive User Manual ...
Page 9: ...VI MD65 AC Drive User Manual ...
Page 11: ...VIII MD65 AC Drive User Manual ...
Page 13: ...1 2 MD65 AC Drive User Manual ...
Page 47: ...6 12 MD65 AC Drive User Manual ...
Page 119: ...10 12 MD65 AC Drive User Manual ...
Page 123: ...A 4 MD65 AC Drive User Manual ...
Page 129: ...B 6 MD65 AC Drive User Manual ...
Page 135: ...C 6 MD65 AC Drive User Manual ...
Page 139: ...D 4 MD60 AC Drive User Manual ...
Page 149: ...Accessories E 10 ...
Page 179: ...PID Set Up I 10 ...
Page 184: ......
Page 185: ......
Page 186: ......