I-4
MD65 AC Drive User Manual
PID Feedback Sel (A133) is used to select the source of the PID
feedback.
Table I.2 – PID Feedback Sel (A133) Options
Analog PID Reference Signals
Parameters Anlg ln 0-10V Lo (A110) and Anlg ln 0-10V Hi (A111)
are used to scale or invert an analog PID Reference.
Important: Firmware version FRN 1.xx does not support
PID Feedback scaling from an analog input.
Examples
Scale Function
For a 0-5 volt signal, the following parameter settings are used so
that a 0 volt signal = 0% PID Reference and a 5 volt signal = 100%
PID Reference.
•
Angl ln 0-10V Lo (A110) = 0.0%
•
Angl ln 0-10V Hi (A111) = 50.0%
•
PID Ref Sel (A132) = 0 “0-10V Input”
Option
Description
0 “0-10V Input”
Selects the 0-10V Input (default setting). Note that the PID will
not function with a bipolar analog input. It will ignore any
negative voltages and treat them like a zero.
1 “4-20mA Input“
Selects the 4-20mA Input.
2 “Comm Port”
The reference word from a communication network such as
Modbus RTU or DeviceNet becomes the PID Feedback. The
value sent over the network is scaled so that P035 [Maximum
Freq] x 10 = 100% Feedback. For example, with [Maximum
Freq] = 60 Hz, a value of 600 sent over the network would
represent 100% Feedback.
0
10
20
30
40
50
60
70
80
90 100
PID Reference (%)
Input V
olts
2
4
6
8
10
12
Summary of Contents for Reliance Electric MD65
Page 2: ...Instruction Manual MD65 AC Drive User Manual Version 2 0 D2 3519 2 ...
Page 7: ...IV MD60 AC Drive User Manual ...
Page 9: ...VI MD65 AC Drive User Manual ...
Page 11: ...VIII MD65 AC Drive User Manual ...
Page 13: ...1 2 MD65 AC Drive User Manual ...
Page 47: ...6 12 MD65 AC Drive User Manual ...
Page 119: ...10 12 MD65 AC Drive User Manual ...
Page 123: ...A 4 MD65 AC Drive User Manual ...
Page 129: ...B 6 MD65 AC Drive User Manual ...
Page 135: ...C 6 MD65 AC Drive User Manual ...
Page 139: ...D 4 MD60 AC Drive User Manual ...
Page 149: ...Accessories E 10 ...
Page 179: ...PID Set Up I 10 ...
Page 184: ......
Page 185: ......
Page 186: ......