RS485 (MDI) Protocol
F-5
Writing (06) Reference
The Speed Reference to a MD65 drive can be controlled via the
network by sending Function Code 06 writes to register address
8193 (Reference). P038 (Speed Reference) must be set to 5
“RS485 (MDI) Port” in order to accept the Speed Reference.
Reading (03) Logic Status Data
The MD65 Logic Status data can be read via the network by
sending Function Code 03 reads to register address 8448 (Logic
Status).
Table F.4 – Reference
Reference
Address
(Decimal)
Description
8193
A decimal value entered as xxx.x where the decimal point is
fixed. For example, a decimal “100” equals 10.0 Hz and “543”
equals 54.3 Hz.
Table F.5 – Logic Status Data
Logic Status
Address
(Decimal)
Bit(s)
Description
8448
0
1 = Ready, 0 = Not Ready
1
1 = Active (Running), 0 = Not Active
2
1 = Cmd Forward, 0 = Cmd Reverse
3
1 = Rotating Forward, 0 = Rotating Reverse
4
1 = Accelerating, 0 = Not Accelerating
5
1 = Decelerating, 0 = Not Decelerating
6
1 = Alarm, 0 = No Alarm
7
1 = Faulted, 0 = Not Faulted
8
1 = At Reference, 0 = Not At Reference
9
1 = Reference Controlled by Comm
10
1 = Operation Cmd Controlled by Comm
11
1 = Parameters have been locked
12
Digital Input 1 Status
13
Digital Input 2 Status
14
Not Used
15
Not Used
Summary of Contents for Reliance Electric MD65
Page 2: ...Instruction Manual MD65 AC Drive User Manual Version 2 0 D2 3519 2 ...
Page 7: ...IV MD60 AC Drive User Manual ...
Page 9: ...VI MD65 AC Drive User Manual ...
Page 11: ...VIII MD65 AC Drive User Manual ...
Page 13: ...1 2 MD65 AC Drive User Manual ...
Page 47: ...6 12 MD65 AC Drive User Manual ...
Page 119: ...10 12 MD65 AC Drive User Manual ...
Page 123: ...A 4 MD65 AC Drive User Manual ...
Page 129: ...B 6 MD65 AC Drive User Manual ...
Page 135: ...C 6 MD65 AC Drive User Manual ...
Page 139: ...D 4 MD60 AC Drive User Manual ...
Page 149: ...Accessories E 10 ...
Page 179: ...PID Set Up I 10 ...
Page 184: ......
Page 185: ......
Page 186: ......