4-44
Configuring the I/O
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Figure 4.48 MicroLogix 1100 Message Configuration Screens for the Logic
Command, Reference, and DL To Net Datalinks
General Tab Box
Setting
This Controller (data for MicroLogix 1100)
Channel
1 (integral). Controller port to which the EtherNet/IP network is connected.
Communication Command
500CPU Write. The controller type and command type for the controller to read or write data.
Since the MicroLogix 1100 is part of the SLC-500 controller family, the “500CPU” controller
type was selected. The “Write” command type was selected to write data to the drive.
Data Table Address
(1)
N20:37. An unused controller data table address containing the data to be written to the drive.
Size in Elements
(2)
36. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
Target Device (data for adapter/drive)
Message Timeout
5. Message timeout duration in seconds.
Data Table Address
(3)
N45:0. Specific starting address of the destination file in the drive.
Routing Information File
RI9:2. An unused routing information file for the controller.
MultiHop Tab Box
Setting
To Address
10.91.100.79. The IP address of the adapter connected to the drive.
(1)
For details on data table addresses for this example project, refer to
(2)
For details to determine element size for a specific drive, refer to
Understanding Controller Data Table Addresses on page 5-14
.
(3)
For N-File details, see
.
TIP: If the controller is controlling more than one drive, it is
recommended to intersperse the control I/O messaging for each drive to
conserve network bandwidth and decrease response time. That is,
sequence the message instructions for each drive so that its group of
messages will occur at a different time than those for another drive.