Configuring the I/O
4-21
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
PLC-5 Example
Important: The PLC-5 must be Series E (Rev. D.1 or higher) to support
the MultiHop feature that routes messaging to the drive.
Example Network
After the adapter is configured, the connected drive and adapter will be
a single node on the network. This section provides the steps needed to
configure a simple EtherNet/IP network (see
). In our
example, we will configure a PLC-5/40E controller to communicate
with a drive using Logic Command/Status, Reference/Feedback, and 32
Datalinks (16 to read/16 to write) over the network.
Figure 4.25 PLC-5 Example EtherNet/IP Network
Configuring Parameters for Network I/O
Since the I/O for the drive is message-based, there is no need to
configure any I/O inside the RSLogix 5 (v7 or higher) project until
using the I/O as described in
.
However, to get the adapter to operate with the I/O created in
,
we need to configure the adapter to accept the I/O and the drive to point
to the appropriate Datalinks.
Since the adapter always uses the 32-bit Logic Status and 32-bit
Feedback, at least two 32-bit words must be accounted for in the
controller input image. The adapter also uses the 32-bit Logic
Command and 32-bit Reference, requiring at least two 32-bit words that
must be accounted for in the controller output image. If any or all of the
drive’s sixteen 32-bit Datalinks are used (see
Custom Peer I/O Configuration on
•
An additional 32-bit word for each [DL From Net xx] Datalink used
to write to drive or peripheral parameters must be accounted for in
the controller input image.
IP Address 10.91.100.80
PLC-5/40E Controller with
Embedded Ethernet
IP Address 10.91.100.79
PowerFlex 755 Drive with
Embedded EtherNet/IP Adapter
Computer with
Ethernet Connection