3-6
Configuring the Adapter
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Figure 3.7
Edit IP Addr Cfg 1 HIM Screen
3. Reset the adapter by power cycling the drive or by using the HIM’s
Reset Device function located in the drive’s DIAGNOSTIC folder.
The ENET status indicator will be solid green or flashing green if
the IP address is correctly configured.
Setting a Subnet Mask Using Parameters
1. Verify that Parameter 36 - [BOOTP] is set to “0” (Disabled). This
parameter must be set to Disabled to configure the subnet mask
using the adapter parameters.
2. Set the value of Parameters 42 - [Subnet Cfg 1] through 45 -
[Subnet Cfg 4] to the desired value for the subnet mask.
Figure 3.8
Edit Subnet Cfg 1 HIM Screen
3. Reset the adapter by power cycling the drive or by using the HIM’s
Reset Device function located in the drive’s DIAGNOSTIC folder.
Setting a Gateway Address for the Adapter Using Parameters
1. Verify that Parameter 36 - [BOOTP] is set to “0” (Disabled). This
parameter must be set to Disabled to configure the gateway address
using the adapter parameters.
2. Set the value of Parameters 46 - [Gateway Cfg 1] through 49 -
[Gateway Cfg 4] to the IP address of the gateway device.
Default = 0.0.0.0
255 . 255 . 255 . 255
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]