Adapter Parameters
B-5
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
54 [Comm Flt Action]
Sets the action that the adapter and drive will
take if the adapter detects that I/O
communications have been disrupted. This
setting is effective only if I/O that controls the
drive is transmitted through the adapter.
Default:
0 = Fault
Values:
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Type:
Read/Write
Reset Required: No
55 [Idle Flt Action]
Sets the action that the adapter and drive will
take if the adapter detects that the controller is
in program mode or faulted. This setting is
effective only if I/O that controls the drive is
transmitted through the adapter.
Default:
0 = Fault
Values:
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Type:
Read/Write
Reset Required: No
56 [Peer Flt Action]
Sets the action that the adapter and drive will
take if the adapter detects that Peer I/O
communications have been disrupted. This
setting is effective only if I/O is transmitted
through the adapter.
Default:
0 = Fault
Values:
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Type:
Read/Write
Reset Required: No
Parameter
No. Name and Description
Details
!
ATTENTION: Risk of injury or equipment damage exists. Parameter 54 -
[Comm Flt Action] lets you determine the action of the adapter and
connected drive if I/O communications are disrupted. By default, this
parameter faults the drive. You can set this parameter so that the drive
continues to run. Precautions should be taken to ensure that the setting of
this parameter does not create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds correctly to
various situations (for example, a disconnected cable).
!
ATTENTION: Risk of injury or equipment damage exists. Parameter 55 -
[Idle Flt Action] lets you determine the action of the adapter and
connected drive when the controller is idle. By default, this parameter faults
the drive. You can set this parameter so that the drive continues to run.
Precautions should be taken to ensure that the setting of this parameter
does not create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds correctly to
various situations (for example, a controller in idle state).
!
ATTENTION: Risk of injury or equipment damage exists. Parameter 56 -
[Peer Flt Action] lets you determine the action of the adapter and
connected drive if the adapter is unable to communicate with the
designated peer. By default, this parameter faults the drive. You can set
this parameter so that the drive continues to run. Precautions should be
taken to ensure that the setting of this parameter does not create a risk of
injury or equipment damage. When commissioning the drive, verify that
your system responds correctly to various situations (for example, a
disconnected cable).