3-20
Programming and Parameters
SPE
ED COMMA
N
D
Sp
eed Ref
er
ence
s
096
[TB Man Ref Sel]
Sets the manual speed reference source
when a digital input is configured for
“Auto/Manual.”
(1)
“Analog In 2” is not a valid selection if it
was selected for any of the following:
- [Trim In Select]
- [PI Feedback Sel]
- [PI Reference Sel]
- [Current Lmt Sel]
- [Sleep-Wake Ref]
Default:
Options:
1
1
2
3-8
9
“Analog In 1”
“Analog In 1”
“Analog In 2”
(1)
“Reserved”
“MOP Level”
097
[TB Man Ref Hi]
Scales the upper value of the [TB Man
Ref Sel] selection when the source is an
analog input.
Default:
Min/Max:
Units:
[Maximum Speed]
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
098
[TB Man Ref Lo]
Scales the lower value of the [TB Man
Ref Sel] selection when the source is an
analog input.
Default:
Min/Max:
Units:
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
099
[Pulse Input Ref]
Displays the pulse input value as seen at
terminals 5 and 6 of the Encoder
Terminal Block, if [Encoder Z Chan],
parameter 423 is set to “Pulse Input.”
Default:
Min/Max:
Units:
Read Only
–/+420.0 Hz
–/+25200.0 RPM
0.1 Hz
0.1 RPM
Dis
cre
te
Spe
eds
100
[Jog Speed 1]
Sets the output frequency when Jog
Speed 1 is selected.
Default:
Min/Max:
Units:
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
101
102
103
104
105
106
107
[Preset Speed 1]
[Preset Speed 2]
[Preset Speed 3]
[Preset Speed 4]
[Preset Speed 5]
[Preset Speed 6]
[Preset Speed 7]
Provides an internal fixed speed
command value. In bipolar mode
direction is commanded by the sign of
the reference.
Default:
Min/Max:
Units:
5.0 Hz/150 RPM
10.0 Hz/300 RPM
20.0 Hz/600 RPM
30.0 Hz/900 RPM
40.0 Hz/1200 RPM
50.0 Hz/1500 RPM
60.0 Hz/1800 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
108
[Jog Speed 2]
Sets the output frequency when Jog
Speed 2 is selected.
Default:
Min/Max:
Units:
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
Fi
le
Gr
ou
p
No.
Parameter Name & Description
See
page 3-2
for symbol descriptions
Values
Relate
d
Summary of Contents for Allen-Bradley PowerFlex 700 B Series
Page 10: ...P 6 Overview Notes ...
Page 36: ...1 26 Installation Wiring Notes ...
Page 118: ...3 78 Programming and Parameters Notes ...
Page 162: ...A 28 Supplemental Drive Information Notes ...
Page 227: ......