Appendix
A
Supplemental Drive Information
For information on . .
See page . .
Drive, Fuse & Circuit Breaker Ratings
Specifications
Category
Specification
Agency
Certification
Listed to UL508C and CAN/CSA-C2.2 No. 14-M91.
Marked for all applicable European Directives
(1)
EMC Directive (89/336/EEC)
EN 61800-3 Adjustable Speed electrical power drive systems
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power Installations
Certified to AS/NZS, 1997 Group 1, Class A.
The drive is also designed to meet the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and
Operation of Adjustable Speed Drive Systems.
IEC 146 - International Electrical Code.
(1)
Applied noise impulses may be counted in addition to the standard pulse train causing erroneously
high [Pulse Freq] readings.
Category
Specification
Protection
Drive
200-
208V
240V 380/
400V
480V
600V
Frames 0-4
600/690V
Frames 5-6
AC Input Overvoltage Trip:
285VAC 285VAC
570VAC 570VAC 716VAC
818VAC
AC Input Undervoltage Trip:
120VAC 138VAC
233VAC 280VAC 345VAC
345VAC
Bus Overvoltage Trip:
405VDC 405VDC 810VDC 810VDC 1013VDC 1162VAC
Bus Undervoltage Shutoff/Fault:
153VDC 153VDC 305VDC 305VDC 381VDC
437VAC
Nominal Bus Voltage:
281VDC 324VDC 540VDC 648VDC 810VDC
932VAC
All Drives
Heat Sink Thermistor:
Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Overcurrent Trip:
Hardware Overcurrent Trip:
200% of rated current (typical)
220-300% of rated current (dependent on drive rating)
Line transients:
up to 6000 volts peak per IEEE C62.41-1991
U
c
US
L
N223
Summary of Contents for Allen-Bradley PowerFlex 700 B Series
Page 10: ...P 6 Overview Notes ...
Page 36: ...1 26 Installation Wiring Notes ...
Page 118: ...3 78 Programming and Parameters Notes ...
Page 162: ...A 28 Supplemental Drive Information Notes ...
Page 227: ......