1-18
Installation/Wiring
Encoder Terminal Block
Table 1.H Encoder Terminal Designations
Figure 1.8 Sample Encoder Wiring
Hardware Enable Circuitry
By default, the user can program a digital input as an Enable input. The
status of this input is
interpreted by drive software
. If the application
requires the drive to be disabled
without
software interpretation, a
“dedicated” hardware enable configuration can be utilized. This is done
by removing a jumper and wiring the enable input to “Digital In 6” (see
below).
1.
Remove the I/O Control Cassette &
cover as described on
2.
Locate & remove Jumper J10 on the
Main Control Board (see diagram).
3.
Re-assemble cassette.
4.
Wire Enable to “Digital In 6” (see
).
5.
Verify that [Digital In6 Sel],
parameter 366 is set to “1, Enable.”
No.
Description
(refer to
for encoder specifications)
See “Detail” in
8
+12V
(1)
DC Power
(1)
Jumper sele5/12V is available on 20B-ENC-2 Encoder Boards only.
Internal power source
250 mA.
7
+12V
DC Return (Common)
6
Encoder Z (NOT)
Pulse, marker or registration
input.
(2)
(2)
Z channel can be used as a pulse input while A & B are used for encoder.
5
Encoder Z
4
Encoder B (NOT)
Quadrature B input.
3
Encoder B
2
Encoder A (NOT)
Single channel or
quadrature A input.
1
Encoder A
8
1
I/O
Connection Example
I/O
Connection Example
Encoder
Power –
Internal Drive
Power
Internal (drive)
12V DC,
250mA
Encoder
Power –
External
Power
Source
Encoder
Signal –
Single-Ended,
Dual Channel
Encoder
Signal –
Differential,
Dual
Channel
Common
+12V DC
(250 mA)
1
2
3
4
5
6
7
8
to SHLD
+
Common
External
Power
Supply
to
SHLD
B
B NOT
A NOT
A
Z
Z NOT
to SHLD
to Power Supply
Common
1
2
3
4
5
6
7
8
to SHLD
1
2
3
4
5
6
7
8
B
Z
A NOT
B NOT
Z NOT
A
E
N
A
B
LE
JU
M
P
E
R
J1
0
Summary of Contents for Allen-Bradley PowerFlex 700 B Series
Page 10: ...P 6 Overview Notes ...
Page 36: ...1 26 Installation Wiring Notes ...
Page 118: ...3 78 Programming and Parameters Notes ...
Page 162: ...A 28 Supplemental Drive Information Notes ...
Page 227: ......