Programming and Parameters
3-55
INPUTS & OUTPUTS
Dig
ita
l I
n
pu
ts
361
362
363
364
365
366
[Digital In1 Sel]
[Digital In2 Sel]
[Digital In3 Sel]
[Digital In4 Sel]
[Digital In5 Sel]
[Digital In6 Sel]
(10)
Selects the function for the digital inputs.
(1)
Speed Select Inputs.
To access Preset Speed 1, set [Speed
Ref x Sel] to “Preset Speed 1”.
Type 2 Alarms - Some digital input
programming may cause conflicts that
will result in a Type 2 alarm. Example:
[Digital In1 Sel] set to “5, Start” in 3-wire
control and [Digital In2 Sel] set to 7
“Run” in2-wire. See
for info on
resolving this type of conflict.
(3)
When [Digital Inx Sel] is set to option 2
“Clear Faults” the Stop button cannot be
used to clear a fault condition.
(4)
Typical 3-Wire Inputs - Only 3-wire
functions are allowed. Including 2-wire
selections will cause a type 2 alarm.
(5)
Typical 2-Wire Inputs - Only 2-wire
functions can be chosen. Including
3-wire selections will cause a type 2
alarm. See
for conflicts.
(6)
Auto/Manual - Refer to
for details.
(7)
Opening an “Enable” input will cause
the motor to coast-to-stop, ignoring any
programmed Stop modes.
(8)
“Dig In ConflictB” alarm will occur if a
“Start” input is prog. without a “Stop” input.
(9)
Refer to the Sleep-Wake Mode
Attention statement on
.
continued
Default:
Default:
Default:
Default:
Default:
Default:
Options:
4
5
18
15
16
17
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15-17
18
19
20
21
22
23
24
25
26
27
28
29
30
31-33
34
35
36
37
38
39
40
41-42
43
44
45
46
47
48
49
50
51
52-56
57
“Stop – CF”
“Start”
“Auto/ Manual”
“Speed Sel 1”
“Speed Sel 2”
“Speed Sel 3”
“Not Used”
“Enable”
(7,9)
“Clear Faults”(CF)
(3)
“Aux Fault”
“Stop – CF”
(9)
“Start”
(4, 8)
“Fwd/ Reverse”
(4)
“Run”
(5, 9)
“Run Forward”
(5)
“Run Reverse”
(5)
“Jog1”
“Jog Forward”
(5)
“Jog Reverse”
(5)
“Stop Mode B”
“Bus Reg Md B”
“Speed Sel 1-3”
(1)
“Auto/ Manual”
(6)
“Local”
“Acc2 & Dec2”
“Accel 2”
“Decel 2”
“MOP Inc”
(12)
“MOP Dec”
(12)
“Excl Link”
(12)
“PI Enable”
“PI Hold”
“PI Reset”
“Pwr Loss Lvl”
“Precharge En”
(12)
“Spd/Trq Sel1-3”
(2)
“Jog 2”
“PI Invert”
“Torque Setpt 1”
(12)
“Flt/MicroPos”
(11, 12)
“Fast Stop”
(12)
“Decel Limit”
“End Limit”
“UserSet Sel1-2”
(13)
“Run Level”
“RunFwd Level”
“RunRev Level”
(12)
“Run w/Comm”
(12)
“Hold Step”
(12)
“Redefine Pos”
(12)
“Find Home”
(12)
“Home Limit”
(12)
“Vel Override”
(12)
“Pos Sel 1-5”
(12)
“Prof Input”
(12)
Fi
le
Gr
ou
p
No.
Parameter Name & Description
See
page 3-2
for symbol descriptions
Values
Relate
d
3
2
1
Auto Reference Source
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
Reference A
Reference B
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7
(2)
3
2
1
Spd/Trq Mode
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
Zero Torque
Spd Reg
Torque Reg
Min Spd/Trq
Max Spd/Trq
Sum Spd/Trq
Absolute
Pos/Spd Prof