4-16
Troubleshooting
Select testpoint with [Testpoint x Sel], parameters 234/236. Values can
be viewed with [Testpoint x Data], parameters 235/237.
Testpoint Codes and Functions
No.
(1)
(1)
Enter in [Testpoint x Sel].
Description
Units
Values
Minimum
Maximum
Default
01
DPI Error Status
1
0
255
0
02
Heatsink Temp
0.1 degC
–100.0
100.0
0
03
Active Cur Limit
1
0
32767
0
04
Active PWM Freq
1 Hz
2
10
4
05
Life MegaWatt Hr
(2)
(2)
Use the equatio
n
below to calculate total Lifetime MegaWatt Hours.
0.0001 MWh 0
214748.3647
0
06
Life Run Time
0.0001 Hrs
0
214748.3647
0
07
Life Pwr Up Time
0.0001 Hrs
0
214748.3647
0
08
Life Pwr Cycles
1
0
4294967295
0
09
Life MW-HR Fract
1
0
4294967295
0
10
MW-HR Frac Unit
1
0
4294967295
0
11
MCB Life Time
0.0001 Hrs
0
214748.3647
0
12
Raw Analog In 1
1
0
0
13
Raw Analog In 2
1
0
0
16
CS Msg Rx Cnt
1
0
65535
0
17
CS Msg Tx Cnt
1
0
65535
0
18
CS Timeout Cnt
1
0
255
0
19
CS Msg Bad Cnt
1
0
255
0
22
PC Msg Rx Cnt
1
0
65535
0
23
PC Msg Tx Cnt
1
0
65535
0
24-29
PC1-6 Timeout Cnt
1
0
255
0
30
CAN BusOff Cnt
1
0
65535
0
31
No. of Analog Inputs
1
0
x
0
32
Raw Temperature
1
0
65535
0
33
MTO Norm Mtr Amp
0.1 Amps
0
65535
0
34
DTO-Cmd Frequency
1
0
420
0
35
DTO-Cmd Cur Lim
0.1
0
0
36
DTO-Cmd DC Hold
1
0
32767
0
37
Control Bd Temp
0.1
0.0
60.0
0.0
Value of Code 9
Value of Code 10
---------------------------------
0.1
×
Value of Code 5
+
Total Lifetime MegaWatt Hours
=
Summary of Contents for Allen-Bradley PowerFlex 700 B Series
Page 10: ...P 6 Overview Notes ...
Page 36: ...1 26 Installation Wiring Notes ...
Page 118: ...3 78 Programming and Parameters Notes ...
Page 162: ...A 28 Supplemental Drive Information Notes ...
Page 227: ......