A-4
Supplemental Drive Information
PowerFlex 700 Watts Loss (Rated Load, Speed & PWM)
(1)
(1)
Worst case condition including Vector Control board, HIM and Communication Module
Voltage
ND HP
External Watts
Internal Watts
Total Watts Loss
240V
0.5
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
9
22
38
57
97
134
192
276
354
602
780
860
1132
1296
1716
1837
37
39
39
41
82
74
77
92
82
96
96
107
138
200
277
418
46
61
77
98
179
208
269
368
436
698
876
967
1270
1496
1993
2255
480V
0.5
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
11
19
31
46
78
115
134
226
303
339
357
492
568
722
821
1130
1402
1711
1930
42
44
45
46
87
79
84
99
91
102
103
117
148
207
286
397
443
493
583
53
63
76
93
164
194
218
326
394
441
459
610
717
930
1107
1479
1845
2204
2512
600V
0.5
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
9
14
25
41
59
83
109
177
260
291
324
459
569
630
1053
1467
1400
1668
37
40
40
42
83
75
77
93
83
95
95
109
141
195
308
407
500
612
46
54
65
83
142
157
186
270
343
385
419
569
710
825
1361
1874
1900
2280