Chapter 3 EtherNet/IP Operation
Figure 32 - Armor PowerFlex Drive in a DLR Configuration
Protected Operations Mode
To maintain the secure operation of your drive, operations that can disrupt
drive operation are restricted based on its operating mode.
This drive is in protected mode when: there are standard or safety I/O
connections, the drive is running.
Distributed I/O
1756-EN2T
1756 I/O Modules
1794-AENT
1794 I/O
1769-L23Ex
1769-L3xE
1734-AENT
Workstation
PowerFlex
Drive
Armor PowerFlex
Drive
1783-ETAP
Workstation
1783-ETAP
1783-ETAP
PanelView Terminal
1738-AENTR
1738 I/O Modules
1734-AENTR
1734 I/O Modules
1756-EN2TR
1756 I/O Modules
Device Level Ring
It is recommended that no more than 50 nodes are on a single DLR. If your
application requires more than 50 nodes, it is recommended that the DLR
networks be segmented.
With smaller networks:
• There is better management of traffic on the network.
• The networks are easier to maintain.
• There is a lower likelihood of multiple faults.