Chapter 7 Configure the Armor PowerFlex Drive
Figure 78 - S-Curve Examples
Output Frequency
5. Enter your minimum and maximum Output Frequency settings.
Configure Stop Control
The Stop Control page includes attributes related to the stop control of the
motor.
1. Click Stop Control.
S-Curve Time
Total Time to Accelerate = Accel Time + S-Curve Time
50% S-Curve
Target
vel
Target
vel/2
S-Curve Time = Accel Time
Total Time to Accelerate = Accel Time + S-Curve Time
100% S-Curve
Target
vel