5. COMMUNICATION DATA LIST
IMR02F04-E1
51
No. Name
RKC
Iden-
tifier
Modbus
register
address
Attri-
bute
Data range
Factory set
value
HEX
DEC
46 Alarm 1 type
XA
0111
273
R/W 0: None
1: Process high
2: Process low
Based on model
code.
When not
specifying: 1
47 Alarm 1 hold action
WA
0112
274
R/W 0: OFF
1: Hold action ON
Based on model
code.
When not
specifying: 0
48 Alarm 1 interlock
QA
0113
275
R/W 0: Unused (OFF)
1: Used
0
49 Alarm 1
energized/de-energized
NA 0114
276
R/W 0: Energized
1: De-energized
0
50 Alarm 1 differential gap
HA
0115
277
R/W 0 to Input span
Varies with the setting of the Input
decimal point position.
2
51 Alarm 1 delay timer
TD
0116
278
R/W 0.0 to 600.0 seconds
0.0
52 Alarm 1 action at
input error
OA 0117
279
R/W 0: Normal alarm action
1: Forced alarm ON when
temperature
measured
value
exceeds the input error
determination point (high or low
limit).
0
53 Alarm 2 type
XB
0118
280
R/W 0: None
1: Process high
2: Process low
Based on model
code.
When not
specifying: 2
54 Alarm 2 hold action
WB
0119
281
R/W 0: OFF
1: Hold action ON
Based on model
code.
When not
specifying: 0
55 Alarm 2 interlock
QB
011A
282
R/W 0: Unused (OFF)
1: Used
0
56 Alarm 2
energized/de-energized
NB 011B
283
R/W 0: Energized
1: De-energized
0
57 Alarm 2 differential gap
HB
011C
284
R/W 0 to Input span
Varies with the setting of the Input
decimal point position.
2
58 Alarm 2 delay timer
TG
011D
285
R/W 0.0 to 600.0 seconds
0.0
59 Alarm 2 action at
input error
OB 011E
286
R/W 0: Normal alarm action
1: Forced alarm ON when
temperature
measured
value
exceeds the input error
determination point (high or low
limit).
0
60 Alarm 3 type
XC
011F
287
R/W 0: None
1: Process high
2: Process low
Based on model
code.
When not
specifying: 0