5. COMMUNICATION DATA LIST
IMR02F04-E1
54
5.3 The communication data which will be initialized or
changed, if the communication data are changed
Before changing any communication data setting, always record all communication data
settings. And after the change, always check all communication data settings by comparing
them with the record taken before the change.
The communication data which will be initialized if the Input type is changed
When Input type (RKC communication: XI, Modbus: 00FAH) is changed
The following communication data will be changed to factory default values according to the new setting.
Name
Factory set value
Gain setting
Factory set value varies depending on the type of input.
Our CZ-100P/CZ-200P (Standard): 1.500
Our CZ-100P/CZ-200P (Explosionproof):
1.500
Our CZ-100P/CZ-200P (Standard)
[Loose nut: 0.0 to 0.5 MPa, Fixed nut: 0 to 5 MPa]: 0.650
Our CZ-100P/CZ-200P (Explosionproof)
[Loose nut: 0.0 to 0.5 MPa, Fixed nut: 0 to 5 MPa]: 0.650
3.33 mV/V output type
(Pressure sensor made by other companies):
3.330
Display unit
1 (MPa)
Input decimal point position
0 (No decimal place)
Pressure display high
50
Pressure display low
0
PV bias
0
PV ratio
1.000
Alarm 1 set value
50
Alarm 2 set value
0
Alarm 3 set value
50
Alarm 4 set value
50
Input error determination point
(high)
53
Input error determination point
(low)
2
Burnout direction
0 (Upscale)
Transmission output scale high
50
Transmission output scale low
0
Alarm 1 hold action to
Alarm 4 hold action
0 (OFF)
Alarm 1 interlock to
Alarm 4 interlock
0 (Unused, OFF)
Alarm 1 energized/de-energized to
Alarm 4 energized/de-energized
0 (Energized)
Alarm 1 differential gap to
Alarm 4 differential gap
2
Alarm 1 delay timer to
Alarm 4 delay timer
0.0 second