5. COMMUNICATION DATA LIST
IMR02F04-E1
56
The communication data which will be initialized if the Alarm type is
changed
When Alarm 1 type (RKC communication: XA, Modbus: 0111H) is changed
The following communication data will be changed to factory default values according to the new setting.
Name
Factory set value
Alarm 1 set value
50
Varies with the setting of the Input decimal point position.
Alarm 1 hold action
0 (OFF)
Alarm 1 interlock
0 (Unused, OFF)
Alarm 1 energized/de-energized
0 (Energized)
Alarm 1 differential gap
2
Varies with the setting of the Input decimal point position.
Alarm 1 delay timer
0.0 second
When Alarm 2 type (RKC communication: XB, Modbus: 0118H) is changed
The following communication data will be changed to factory default values according to the new setting.
Name
Factory set value
Alarm 2 set value
0
Varies with the setting of the Input decimal point position.
Alarm 2 hold action
0 (OFF)
Alarm 2 interlock
0 (Unused, OFF)
Alarm 2 energized/de-energized
0 (Energized)
Alarm 2 differential gap
2
Varies with the setting of the Input decimal point position.
Alarm 2 delay timer
0.0 second
When Alarm 3 type (RKC communication: XC, Modbus: 011FH) is changed
The following communication data will be changed to factory default values according to the new setting.
Name
Factory set value
Alarm 3 set value
50
Varies with the setting of the Input decimal point position.
Alarm 3 hold action
0 (OFF)
Alarm 3 interlock
0 (Unused, OFF)
Alarm 3 energized/de-energized
0 (Energized)
Alarm 3 differential gap
2
Varies with the setting of the Input decimal point position.
Alarm 3 delay timer
0.0 second