5. COMMUNICATION DATA LIST
IMR02F04-E1
52
No. Name
RKC
Iden-
tifier
Modbus
register
address
Attri-
bute
Data range
Factory set
value
HEX
DEC
61 Alarm 3 hold action
WC
0120
288
R/W 0: OFF
1: Hold action ON
Based on model
code.
When not
specifying: 0
62 Alarm 3 interlock
QC
0121
289
R/W 0: Unused (OFF)
1: Used
0
63 Alarm 3
energized/de-energized
NC 0122
290
R/W 0: Energized
1: De-energized
0
64 Alarm 3 differential gap
HC
0123
291
R/W 0 to Input span
Varies with the setting of the Input
decimal point position.
2
65 Alarm 3 delay timer
TH
0124
292
R/W 0.0 to 600.0 seconds
0.0
66 Alarm 3 action at
input error
OC 0125
293
R/W 0: Normal alarm action
1: Forced alarm ON when
temperature
measured
value
exceeds the input error
determination point (high or low
limit).
0
67 Alarm 4 type
XD
0126
294
R/W 0: None
1: Process high
2: Process low
Based on model
code.
When not
specifying: 0
68 Alarm 4 hold action
WD
0127
295
R/W 0: OFF
1: Hold action ON
Based on model
code.
When not
specifying: 0
69 Alarm 4 interlock
QD
0128
296
R/W 0: Unused (OFF)
1: Used
0
70 Alarm 4
energized/de-energized
ND 0129
297
R/W 0: Energized
1: De-energized
0
71 Alarm 4 differential gap
HD
012A
298
R/W 0 to Input span
Varies with the setting of the Input
decimal point position.
2
72 Alarm 4 delay timer
TI
012B
299
R/W 0.0 to 600.0 seconds
0.0
73 Alarm 4 action at
input error
OD 012C
300
R/W 0: Normal alarm action
1: Forced alarm ON when
temperature
measured
value
exceeds the input error
determination point (high or low
limit).
0
Unused
012D
·
·
·
013A
301
·
·
·
314