2. HOST COMMUNICATION
IMR02F04-E1
13
1. Turn on the power of the PG500.
2. Go to the Engineering mode.
Press the
key for 2 seconds or more while
pressing the
key at measured value (PV)
monitor until Engineering mode is displayed.
Engineering mode
F10.
28
F10.
8
Measured value
(PV)
MONI
SET
(2 seconds or more)
3. Go to the Function blocks 60 (F60.)
Press the
key twice at function block 10
(F10.) until function block 60 (F60.) is displayed.
Function block 60
(F60.)
F10.
8
F60.
8
Function block 10
(F10.)
(Twice)
4. Set the Communication protocol.
Press the
key at function block 60 (F60.)
until communication protocol is displayed.
Communication
protocol
F60.
8
CMP
Function block 60
(F60.)
SET
Press the
key to set the communication
protocol.
Setting range: 0: RKC communication
1: Modbus
As an example, factory set value “0 (RKC
communication)” is set.
CMP
000
0
Communication
protocol
MONI
0: RKC communication
High-lighted digit
5. Go to the Measured value (PV).
Press and hold the
key for 2 seconds or
more until measured value (PV) is displayed.
Measured value (PV)
F60.
8
28
Function block 60
(F60.)
MONI
(2 seconds or more)
6. Go to the Setup setting mode.
Press the
key while pressing the
key at
measured value (PV) monitor until Setup setting
mode is displayed.
Setup setting mode
Input type
28
InP
Measured value
(PV)
MONI
SET