5. COMMUNICATION DATA LIST
IMR02F04-E1
48
No. Name
RKC
Iden-
tifier
Modbus
register
address
Attri-
bute
Data range
Factory set
value
HEX
DEC
31 Linearizing type
LI
0100
256
R/W 0 to 20
The setting value varies depending
on using pressure sensor.
The setting value varies depending
on using pressure sensor.
When using our CZ-100P or
CZ-200P:
Refer to
Gain setting and
linearizing type (P. 53)
.
When using resistance for sensitivity
adjustment built-in pressure sensor:
Use a factory set value of “0.”
0
32 PV
bias
PB 0101
257
R/W
Input span to
Input span
Varies with the setting of the Input
decimal point position.
0
33 PV digital filter
F1
0102
258
R/W 0.0 to 100.0 seconds (0.0: Unused)
0
34 PV ratio
PR
0103
259
R/W 0.500 to 1.500
The setting value varies depending
on using pressure sensor.
Refer to
Pressure sensor type and
factory set value table
.
1.000
Unused
0104
260
Pressure sensor type and factory set value table
Pressure sensor type
PV ratio set value
When using our CZ-100P or CZ-200P
[Explosionproof specification type]
Set the desired correction factor of our safety barrier RZB-001 to the PV
ratio (Pr). Thus, an indicated error caused by the use of the safety barrier
is corrected. The correction factor is described in the nameplate attached
to the safety barrier (RZB-001).
[Non-explosionproof specification type]
Use a factory set value of “1.000.”
When using resistance for sensitivity
adjustment built-in pressure sensor
The result obtained by auto calibration is reflected to the PV ratio.
Manual full scale adjustment can be performed by changing this PV ratio
value.