5. COMMUNICATION DATA LIST
IMR02F04-E1
46
No. Name
RKC
Iden-
tifier
Modbus
register
address
Attri-
bute
Data range
Factory set
value
HEX
DEC
17 Auto
zero
AZ 00F0
240
R/W 0: Normal state
1: Auto zero execution
When “1” is written, auto zero starts.
When done, the value reverts to “0.”
3: Error
When “0” is written, returns to a
normal state.
0
18 Auto
calibration
FS 00F1
241
R/W 0: Normal state
1: Auto calibration execution
When “1” is written, auto calibration
starts. When done, the value reverts
to “0.”
3: Error
When “0” is written, returns to a
normal state.
This item is valid when using
resistance for sensitivity adjustment
built-in pressure sensor.
0
19 Hold
reset
HR 00F2
242
R/W 0: Hold reset execution
1: Hold state
When “0” is written, the hold reset is
performed. When done, the value
reverts to “1.”
1
20 Interlock
release
IR
00F3
243
R/W 0: Interlock release execution
1: Interlock state
When “0” is written, the interlock is
released. When done, the value
reverts to “1.”
This item is invalid when the alarm 1
to 4 Interlock are set to “0: Unused.”
1
21 Alarm 1 set value
A1
00F4
244
R/W Pressure display low to Pressure
display high
Varies with the setting of the Input
decimal point position.
Signals are output from the alarm
outputs (ALM1 to ALM4) if
exceeding the alarm set value.
This item is invalid when the alarm
type is set to “0: None.”
50
22 Alarm 2 set value
A2
00F5
245
R/W
0
23 Alarm 3 set value
A3
00F6
246
R/W
50
24 Alarm 4 set value
A4
00F7
247
R/W
50
Unused
00F8
248
Unused
00F9
249