background image

VerifEye

®

 Advanced Multi-Circuit Meter

Cat. Nos. 72D48, 72N48, and 73D48

 

INSTALLATION INSTRUCTIONS

ENGLISH

PK-A3387-10-00-0A

Installation 

1.

 

Remove covers.

Screws are provided.

DO NOT EXCEED 346V Line-to-Neutral or 600V Line-to-Line

. This meter is equipped to monitor loads of up to 346V Line-Neutral. Exceeding this voltage will cause damage to the meter and danger to the 

user. Always use a Potential Transformer (PT) for voltages in excess of 346V Line-to-Neutral or 600V Line-to-Line. The VerifEye

®

 is a 600 Volt Over Voltage Category III device.

For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must control conductive pollution and the possibility of condensation or high humidity. Consider the enclosure, the 
correct use of ventilation, thermal properties of the equipment, and the relationship with the environment. Installation Category: CAT II or CAT III

Provide a disconnecting device to disconnect the meter from the supply source. Place this device in close proximity to the equipment, within easy reach of the operator, and mark it as the disconnecting device. 
The disconnecting device shall meet the relevant requirements of IEC 60947-1 and IEC 60947-3, and shall be suitable for the application. In the US and Canada, disconnecting fuse holders can be used. 
Provide over-current protection and a disconnecting device for supply conductors, with approved current-limiting devices suitable for protecting the wiring. If the equipment is used in a manner not specified by 
the manufacturer, the protection provided by the device may be impaired.

For the complete safety information for this product, see the full user guide at www.leviton.com

2.

 

Mount.

Use the enclosure as a template. 

NOTE

:  If the meter is not available to use as a template, see 

the mechanical specifications drawing in the online 
user guide at www.leviton.com.

WARNING: RISK OF ELECTRIC SHOCK, EXPLOSION, 
OR ARC FLASH. DO NOT ENERGIZE METER WITH THE 
VOLTAGE COVER REMOVED. CAREFULLY READ AND 
FOLLOW INSTRUCTIONS.

Connect the voltage leads (L1, L2, L3, and N, as necessary) to 
the meter, through a dedicated disconnect or circuit breaker. 

NOTE:  

Verify the circuit breaker is marked as the disconnect 
breaker for the meter.

Wiring the Meter in a Single-Phase Application:

  

The meter is powered through the voltage between L1 and L2. 
For Single-Phase installations in which no L2 exists, install a  
jumper from N to L2. This connection provides power to the 
meter, maintaining L1-N as the metering voltage reference.

NOTE:  IP30 TOUCH-SAFE

  

(with internal cover installed).

•  Conduit fittings
•  Conduits
•  Blanking plugs

3.

  

Connect.

5.

 

Attatch high-voltage cover.

4.

 

Connect voltage leads.

6.

 

Connect CT and communications wiring.

Communication Verification

The LCD user interface can be used to quickly confirm the settings required for each combination of interface and 
protocol. The interface is intuitive and groups commonly associated registers together. Arrows indicate how to move 
from one menu display to the next. The active menu item is indicated by a blinking character on the LCD. The 

ENTER

 

button is used to select a property, and the 

UP

 and 

DOWN

 buttons are used to select among the values supported by 

the meter.

NOTE

: Verification includes confirmation of BOTH the physical interface settings (serial or ethernet) and the protocol 

(Modbus or BACnet) settings. 

NOTE:

 Changes to the meter configuration are limited to the communication interface, using the LCD. If additional 

changes (such as CT type) are required, they must be made using a software interface.

VerifEye S7 Configuration Utilities/Web Application

If your VerifEye model does not include the LCD user interface, or if you prefer to verify the installation using software, 
then verification is facilitated through the VerifEye S7 Configuration Utilities PC application or the Web App, which 
shares a common design. For an overview of the VerifEye S7 Configuration Utilities or the VerifEye Web App, refer to 
the section on Configuration Details in the full user guide.

Pulse Inputs

Series 7200/7300 meters are equipped with 2 pulse inputs. Pulse counting supports accumulation of consumption data 
from any external meter, using a dry contact (Form A Relay) or open collector outputs. The AcquiSuite Ally pulse inputs 
are compatible with “low-speed” meters. The pulse duration must exceed 50 m/s in both the logic low and high state, 
allowing for a maximum input frequency of 10 Hz. 

Pulse scaling, resetting, and accumulated values are accessed through registers and are “system” in scope. Refer to 
the register list, the S7 Configuration Utilities, or the full user guide for more information.

V

iew Communications

Real Time Values
View Meter Setup
Verify Installation
Log In/Out
About Meter

View Communications

R

eal Time Values

View Meter Setup
Verify Installation
Log In/Out
About Meter

Protocol: BACnet
Baud Rate: 9600
Bits: 8N1

View Communications

Real Time Values

Main Menu

Element A Channels

V
A

kW

100

23.2

2.0

101

22.9

2.0

99.9
22.0

2.0

Element A Channels

kVA

kVAR

kWH

100
100

1234

110

-110

***

111

123
100

NOTE:  

A full navigational map is available in the Appendix 
of the user guide, available at www.leviton.com

PULSE INPUT

1

2

C(+)  E(-)      C(+)  E(-)

L1

N

L2

L3

WARNINGS

•  

RISK OF DEATH OR ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH. DO NOT ENERGIZE METER WITH 
THE VOLTAGE COVER REMOVED. CAREFULLY READ AND FOLLOW INSTRUCTIONS.

•  

TO AVOID FIRE, SHOCK, OR DEATH, 

turn off all power sources supplying the equipment before working on or 

inside the equipment. Use a properly rated voltage sensing device to confirm that power is off.

•  This equipment 

MUST

 be installed and serviced by an electrician or other qualified personnel, with the requisite 

knowledge, training, and experience related to the installation and operation of this equipment, and in accordance 
with applicable codes.

•  Do not depend on this product for voltage indication. 
•  Only install this product on insulated conductors.

CAUTIONS

•  This product is not intended for life or safety applications.
•  Do not install this product in hazardous or classified locations.
•  Mount this product inside a suitable fire and electrical enclosure.
•  If the collector is connected directly to a source of voltage, the pulse isolator will 

immediately burn out and become non-responsive.

WEB 

VERSION

Reviews: