TECHNICAL SPECIFICATIONS

Service Types

Single-Phase; Split-Phase; 3-Phase, 4-Wire (WYE); 3-Phase, 3-Wire (Delta)

Voltage Input

90-346 VAC Line-to-Neutral, 600V Line-to-Line, CAT III

Current Channels

48 channels, 0.525 VAC max, 333 mV CTs, 0-4,000+ Amps (depending on current transducer)

Maximum Current Input

150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with 
RõCoil CTs.

Measurement Type

True RMS, using high-speed digital signal processing (DSP) with continuous sampling

Line Frequency

50-60 Hz

Power

From L1 Phase to L2 Phase. 90-600VAC, RMS, CAT III, 50/60 Hz, 500mA AC Max
Use of 12V auxiliary output requires 100 VAC minimum input voltage.

AC Protection

0.5A Fuse 200kA interrupt capacity

Power Out

Unregulated 12VDC output, 200mA, self-resetting fuse

Waveform Sampling

1.8 kHz

Parameter Update Rate

1 second

Measurements

Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export 
(Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import 
(Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters 
for each phase and system total.

Accuracy

0.2% ANSI C12.20-2010, Class 0.2

Resolution

Values reported in IEEE-754 single-precision floating point format (32 bit).

Indicators

4-line display, tri-color backlight (PhaseChek™)

Pulse Inputs

VerifEye 48 - 2 Inputs 
3.3V sourcing voltage (current limited) to customer dry contact pulse output 
Maximum Pulse Rate of 10 Hz (50 m/s minimum transition time)

Alarm Output

Voltage Phase Loss Alarm (SPDT Relay - 30 VDC) (only)

Communication

Hardware

RS-485, Ethernet, USB (for configuration only)

Supported Protocols

Modbus RTU or BACnet Master Slave Token Passing protocol (MS/TP)

Modbus (using SunSpec IEEE-754 single-precision floating point model)

Modbus TCP

BACnet IP

Max Communication Length (RS485)

1200 meters total length Belden 1120A or equivalent cable,  

with Data Range of 100K bits/second or less 

RS-485 Loading

1/8 unit

Communication Rate (baud)

Modbus: 9600 (Default), 19200, 38400, 57600, 76800, 115200

BACnet: 9600 (Default), 19200, 38400, 76800

Data Bits

8

Parity

None, Even, Odd

Stop Bit

2, 1

Termination

None provided

Mechanical

Wire Connections and Voltage

12-22 AWG 600 VAC. Voltage connection must be #14 AWG or larger and 600 VAC rated.

Mounting

Enclosure or panel mount 

High-Voltage Cover

IP30 (embedded version)

Operating Temperature

-20

o

C to + 60

o

C (-4

o

F to 140

o

F) 

Humidity

5% to 95% non-condensing

Enclosure

ABS plastic, 94-V0 flammability rating, connections sized for 1-inch EMT conduit

Dimensions

(L) 33.7 cm x (W) 25.1 cm x (H) 8.0 cm (13.3 in. x 9.8 in. x 3.1 in.) (enclosure version)

(L) 26.2 cm x (W) 24.1 cm x (H) 8.0 cm (10.3 in. x 9.5 in. x 3.1 in.) (mounting plate version)

PCBA Dimensions

(L) 21.6 cm x (W) 21.6 cm x (H) 6.4 cm (8.5 in. x 8.5 in. x 2.5 in.)

VerifEye S7 Configuration Utilities Minimum System Requirements

Operating System

Windows

®

 7, Windows 8, Windows 10

Communications Port

USB or Ethernet connectivity

Certifications

FCC Part 15, Class A

FCC COMPLIANCE STATEMENT:

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the 
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency 
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio 
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the 
user will be required to correct the interference at his own expense.
Any changes or modifications not expressly approved by Leviton Manufacturing Co., could void the user’s authority to 
operate the equipment.

Wiring
1.

 a. 

Wiring in a 3-Wire, Split-Phase Service Panel

2.

 

Wiring the CTs to the Meter

 b. 

Wiring in a 3-Phase, 4-Wire Service Panel

WARNING: TO AVOID FIRE, SHOCK, OR DEATH, 

turn off all power that is 

supplying the equipment before working on or inside the equipment. Use a properly 
rated voltage sensing device to confirm that power is off.

WARNING: HIGH VOLTAGES THAT ARE LIFE-THREATENING MAY BE 
PRESENT. RISK OF ELECTRIC SHOCK.

 

Configurations shown below are for service types available 
in the 

METER SETUP

 drop-down menu.

EXAMPLE LOADS:

Single-Phase L1-N or L2-N 110 VAC: lighting, appliance, living zone, etc.
Single-Phase L1-L2 220 VAC:

 

water heater, clothes dryer, equipment with no neutral wire, etc.

Split-Phase L1-L2 220 VAC:

 

service entrance, equipment with neutral wire, etc.

3-Wire, Single-Phase used 

on MAINS L1-N, L2-N

(Rogowski coils shown)

Single-Phase 

110VAC plug loads

L1-N or L2-N

Connect the Neutral

wire to V INPUT 1 (N)

on the meter.

Meter is powered

from L1 to L2 on

the V input 1

terminal 

(Label as 

“disconnect”)

.

Single-Phase

220 VAC Plug Load

L1-L2

3-Wire, Single-Phase,

Split-Load

L1-N, L2-N

Configurations shown below are for service types available 
in the 

METER SETUP

 drop-down menu.

3-Wire, 3-Phase used on 
MAINS L1-N, L2-N, L3-N

(Rogowski Coils shown)

Single-Phase

branch loads

L1-N

4-Wire, 3-Phase

WYE load

(Neutral current)

L1-N, L2-N, L3-N

Connect the 
Neutral wire

or Ground wire

to V INPUT 1(N)

on the meter.

Meter power

connects all phases 

to V INPUT 1

terminal 

(Label as 

“disconnect”)

.

3-Wire, 3-Phase

delta load

(no possibility of

neutral current)

L1-N, L2-N(est), L3-N

NOTE:  

The VerifEye Meter Series uses the Neutral terminal as a voltage reference. 
For systems without a Neutral conductor, Leviton suggests connecting a 
Ground wire to this terminal. If the Neutral terminal is left open, Line-to-Line 
measurements will be accurate, but Line-to-Neutral measurements may not 
be symmetric. If a Ground wire is connected to the Neutral terminal, <2mA 
will flow into the Ground wire.

The diagram to the right shows how to connect CTs to the input terminals on the S7200/7300, for each service 
type. For service types that are not specifically listed, choose 

SINGLE-PHASE

 service from the drop-down 

menu and configure each channel individually. The 3-Phase loads that are illustrated on the left side of the 
diagram and the Split-Phase loads on the right side of the diagram are shown as 

examples only

. Elements 

are fully interchangeable on the meter.

NOTE:

  Current and voltage inputs must be installed ‘in phase’ for accurate readings (e.g., CT1 on Line 1, CT2 

on Line 2, etc.). 

Orientation is critical.

 Ensure that all CTs are properly oriented with the line and load, 

as marked. 

Failure to install CTs in the correct orientation and on the correct phase will lead to 

inaccurate meter readings.

CT

CT

CT

CT

CT

CT

L1

N

L2

CT

CT

CT

CT

CT

CT

C

G

K

L

I

J

CH1

CH1

CH1

CH2

CH1

CH3

CH3

CH1

CH1

CH2

CH2

White

White

Black

Black

Red

Red

Blue

N

L1

L2

N

L1

L2

L3

PRIMARY

SECONDARY

VOLTAGE

HIGH

VOLTAGE

3-Phase, 4-Wire Load

L1-N, L2-N, L3-N

3-Phase, 3-Wire

Delta

Single-Phase, 

2-Wire Load

Single-Phase, 2-Wire Load

L1-N

Single-Phase, 2-Wire Load

L2-N

2-Wire, 220 VAC Load

L1-L2

Single-phase, 3-wire, 
Split-Load L1-N, L2-N

M

N

N

L1

L2

L3

L1

L2

L3

N

O

P

D

H

E

F

A

B

TRADEMARK DISCLAIMER: 

Leviton and the Leviton logo are the registered trademarks of Leviton Manufacuring Co., Inc. VerifEye is a Leviton 
trademark registred in the U.S., Canada, and Mexico. Use herein of third party trademarks, service marks, trade names, 
brand names and/or product names are for informational purposes only, are/may be the trademarks of their respective 
owners; such use is not meant to imply affiliation, sponsorship, or endorsement.

Patents covering this product, if any, can be found on Leviton.com/patents.

INDUSTRY CANADA COMPLIANCE STATEMENT:

This device contains license-exempt transmitter/receiver that comply with Innovation, Science and Economic 
Development Canada’s license-exempt RSS(s). Operation is subject to the following two conditions: 
(1) This device may not cause interference.
(2) This device must accept any interference, including interference that may cause undesired operation of the device.

LIMITED 5 YEAR WARRANTY AND EXCLUSIONS

Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the 
purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. 

For details visit www.leviton.com or call 1-800-824-3005.

 This warranty excludes and there is disclaimed liability for labor for removal of 

this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in 
accordance with any labels or instructions. 

There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose

, but if any implied warranty is required by the applicable jurisdiction, the duration 

of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years. 

Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage 

to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation

. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.

FCC SUPPLIER’S DECLARATION OF CONFORMITY:

Models 72D48, 72N48, and 73D48 are sold by Leviton Manufacturing Inc. 201 N Service Rd, Melville, NY 11747. 
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:  
(1) This device may not cause harmful interference, and (2) this device must accept any interference received, 
including interference that may cause undesired operation.

WEB 

VERSION

Reviews: