Storage and disposal 12
CMC-TC Master II
31
EN
12 Storage
and
disposal
12.1.1 Storage
If the device is not being used over a longer period,
we recommend that it be removed from the power
supply and protected from humidity and dust.
Further information concerning the operating condi-
tions is contained in the technical specifications.
12.1.2 Disposal
Because the CMC-TC Master II consists primarily of
the housing and PCB, the unit must be disposed of
through the electronic waste recycling system when
it is no longer required.
13 Customer
service
Should you have any questions (either technical or
general) concerning our product spectrum, please
contact the following service address:
Tel.: +49 (0)2772/505-1855
http://www.rittal.com
E-Mail: [email protected]
Note!
To allow us to process your request
quickly and correctly, please always spe-
cify the article number in the subject line
for e-mails.
Further information and the current operating guides
and updates of the Rittal CMC-TC are available for
download under Security on the Rimatrix5 home-
page.
14 Technical
specifications
Description
CMC-TC
Housing
Housing type
Aluminium housing
Height 65
mm
Width 150
mm
Depth 175
mm
Weight without pack-
ing
approx. 0.6 kg
Potential equalisa-
tion
-
1)
Earthing -
1)
Protection category
IP 20 to EN 60529
Interfaces
Serial interface
2 x RS232 interface
(D-Sub9)
Network interface
1 x RJ-45 socket (10/100
BaseT)
LED display
1 x operating light (rear side)
USB connection
2 x front side, 2 x rear side
VGA connection
1 x VGA connection (front
side)
PS/2 connection
2 x PS/2 connection for key-
board and mouse (rear side)
Operating range
Temperature
+5 to +35 °C
+41 to +95 °F
Humidity
5 – 95 %
Storage temp.
-20 to +70 °C
-4 to +158 °F
Rated voltage
1 x 5 V DC
6 A SELV
Fuses
Fine fuse T2A, 250 V, UL
approval
Network
1 x RJ-45 socket (Ethernet,
10/100 BaseT), shielded
Protocols
Available protocols
- TCP/IP
- SNMP V1.0
(incl. MIB II)
- TELNET
- FTP
- HTTP
Technical specifications
1)
Not required because safety extra-low voltage 5 V DC