Access using Telnet 8
CMC-TC Master II
27
EN
8 Access
using
Telnet
You can also configure the CMC-TC Master II using
Telnet. This requires that you are permitted to have
access with the terminal program using Telnet (see
7.3.9 Configuring Telnet access).
8.1.1 Login using Telnet
This section describes access using Telnet with
Windows.
a. Open the input prompt and enter the command:
telnet <IP-address>.
b. Press "Return" or "Enter" to confirm.
c. Enter for "login" the Telnet login (factory setting:
'cmc'). Press "Return" or "Enter" to confirm.
d. Enter for "Password" the Telnet password (fac-
tory setting: 'cmc'). Press "Return" or "Enter" to
confirm.
8.1.2 Telnet main menu
After login using Telnet, the same main menu as for
access using Hyperterminal appears. Because all
procedures are similar, refer to Chapter 7 Operation.
9 Send
SMS
From software version 2.20 and with an additional
GSM unit, the Master II is able to send an SMS. If
the Master uses a previous software version, you
may download the current software version from the
Rimatrix5 Homepage.
This section describes the installation and commis-
sioning of the GSM unit.
9.1 Connect GSM unit
To connect the GSM unit to the Master II, proceed
as follows.
1
Fig. 41 Connecting the GSM unit (master)
•
Remove the connection cable for the GSM
unit from the accessory pack supplied with
the master. Insert the cable with the D-Sub9
socket at the COM2 interface of the master.
If the connection cable is not part of your
Master II supply scope, you can order the
cable from our telephone hotline at +49
2772 505 9052.
1
3
2
Fig. 42 Connecting the GSM unit
•
The other end of the connection cable has
an RJ12 connector. Insert this connector in
the socket labelled IOIOI on the GSM unit
(1).
•
The SIM card of the mobile telephone oper-
ating company can be inserted in the slot
labelled GSM (2). Please configure before-
hand the SIM card settings as described in
Section 9.2 Setting up the GSM unit on the
master. If this is not done, the SIM card, for
example, could be blocked by an access
with an incorrect PIN.
•
Connect the power pack with the GSM unit
(3). Now insert the mains connector of the
power pack in the socket.