7 Operation
CMC-TC
Master
II
10
EN
7.3 Setting the base configuration
You only need to set the network configuration, the
alarm relay and the trap receiver for the base con-
figuration. You can make further settings from a
browser or using Telnet.
7.3.1 Network configuration
You can use this menu to change your network
settings.
Navigation
Main menu – 1 IP Configuration
Parameter
Explanation
IP Address
Enter your IP address (factory
setting 192.168.0.190).
IP Subnet
Mask
Enter your IP subnet mask
address (factory setting
255.255.255.0).
Default Gate-
way
Enter the IP for the router (fac-
tory setting 0.0.0.0).
To activate the settings, you must activate these
entries.
Navigation
Main menu – D Activate Actual Values
Parameter
Explanation
Activate actual
values
Activate new values: select
“Yes” and press the “Return”
key to accept the settings.
7.3.2 Configuring the trap receiver
To obtain messages and notifications, so-called trap
messages, of the CMC-TC Master II, the IP address
of the console on which the management software
package (e.g. HP OpenView) is installed, must be
entered. The management software must support
the SNMP protocol.
Navigation
Main menu – 2 Trap Receiver Configuration
Parameter
Explanation
IP Trap Re-
ceiver
Enter the IP address of the
messages recipient (factory
setting 0.0.0.0).
Disable
Enable or disable the IP trap
receiver with the
ĸ
(enable)
and
ĺ
(disable) arrow keys.
Enter any other required receivers (maximum four)
in the lines available below.
7.3.3 Configuring SNMP access
Management software that supports SNMP (e.g. HP
Open View or CMC-TC Manager) can access the
CMC-TC Master II via the network.
Navigation
Main menu – 3 Enable SNMP Access
Parameter
Explanation
Enable SNMP
access
Enable or disable the SNMP
access with the
ĸ
and
ĺ
arrow
keys.
7.3.4 Configuring the TFTP access
The TFTP access is used exclusively for uploading
software updates. It can remain deactivated for
normal usage.
Navigation
Main menu – 4 Enable TFTP
Parameter
Explanation
Enable TFTP
Enable or disable TFTP with
the
ĸ
and
ĺ
arrow keys.
7.3.5 Configuring the read/write commu-
nity
To make the settings for a management software
system on the CMC-TC, you must set the commu-
nity of the Processing Unit and the management
software.
Navigation
Main menu – 5 Read Community / 6 Write Com-
munity
Parameter
Explanation
5 Read Com-
munity
Set the read community for the
trap sending. Press the Back-
space key to clear the factory
setting and enter the new
name.
6 Write Com-
munity
Set the write community for the
trap sending. Press the Back-
space key to clear the factory
setting and enter the new
name.