50
Design indication
Indicative diagrams of operation
Wiring diagram - Connection of external additional module
D6
Mixed circuit pump
L N N N
H2 M M U+
1
2
3
Main electronic board
(lower right corner)
D2
Contact probe
for mixed circuits
D5
Mixing valve
ζ
QX23 QX22 QX21
BX21 BX22
1
2
3
Microswitches
for expansion module selection
D4
Electronic programming - Heat generator for additional circuit setting
Description
Parameter
Selection
Standard Value
Value to set
Heating circuit 2
1010
Comfort setpoint
20°C
Between 18 and 22 ° C
1012
Reduced setpoint
16°C
Between 15 and 18 ° C
1020
Heating curve slope
1,5
1.5 Radiators / 0.8 Floor
1041
Flow temp setpoint max
40°C
Radiators 70 ° C / Floor 50 ° C
Configuration
6020
Function extension module 1
-
Heating circuit 2
6032
Relay output QX23 module 1
Pump HC2 Q8
6046
Function input H2 module 1
-
CR2 mode changeover
6047
Contact type 2Hmodule 1
-
Normally open / Normally Closed