25
Gas supply
Sealed sheath
Shut-off valve
Anti-vibration joint
Shut-off valve
Fuel shut-off valve
Requirements and conditions
Gas supply circuit
The gas supply system must be sized for the required flow rate and it must be equipped with
the safety and control devices prescribed by the regulations in force.
In the presence of very long supply networks, it is necessary to contain the pressure drops
and speed in accordance with the provisions of current legislation, in order to avoid the
malfunction of the heat generator burner.
For a correct functioning it is necessary that the static and dynamic pressure of the gas
methane are not lower than 21mbar and 18mbar respectively. In case of higher values, yes
recommends the installation of a suitable pressure reducer.
Indicative diagram of methane gas
Methane gas pipe sizing table
The table is provided for the empirical estimate of the diameter of the pipe, as a function of the equivalent length of the pipe and
installed power.
Installed power Methane gas flow Gas meter type
Maximum equivalent piping lengths (meters)
kW
m
3
/h
3/4"
1"
1" 1/4
1" 1/2
2"
2" 1/2
3”
3” 1/2
65
6.82
G6
8
20
80
150
-
-
-
-
85
8.91
G6
5
15
50
100
-
-
-
-
115
12.06
G10
-
8
30
60
200
-
-
-
130
13.63
G10
-
6
25
50
150
-
-
-
150
15.73
G10
-
5
20
40
120
-
-
-
170
17.83
G16
-
-
15
30
100
-
-
-
195
20.45
G16
-
-
12
25
80
250
-
-
230
24.12
G16
-
-
8
15
60
200
-
-
255
26.74
G25
-
-
6
12
50
180
-
-
260
27.27
G25
-
-
6
12
45
180
-
-
340
35.66
G25
-
-
-
8
30
100
225
-
345
36.18
G25
-
-
-
8
30
100
225
-
450
47.20
G40
-
-
-
5
15
60
120
250
460
48.24
G40
-
-
-
5
15
60
120
250
600
62.93
G40
-
-
-
-
10
35
80
150
The table is purely indicative and simplified, therefore it does not constitute any commitment or responsibility on the part of Rinnai Italia, nor does it intend to replace
the work of the plumbing and heating designer where intervention is required.