24
Errors
display
meaning
action to be taken
ERROR
NO
PELLETS
There are no longer sufficient pellets in the cont-
ainer.
Acknowledge error message and refill pellets.
ERROR
NOT
IGNITED
Ignition cannot be concluded due to lack of ignition
detection.
Acknowledge error message and check pellet
supply container. Open combustion chamber door
and clean fire trough if necessary. Stove can then
be restarted.
ERROR
GRID
DEFECT
The dump grate cannot complete the dump process
provided for.
Acknowledge error message and check for any
blockage of the dump grate at the fire trough.
ERROR
CONVEYOR
DEFECT
One of the two screw motors for pellet conveying
can no longer be actuated.
Acknowledge error message and restart stove.
ERROR
STL
ACTIVATED
The STL (safety temperature limiter) has activated.
The stove overheated and switched off automati-
cally due to a safety risk.
Manually deblock STL at stove rear wall (press)
acknowledge error message and restart stove
FEHLERMELDUNG
FLAMMSENSOR
DEFEKT
The flame temperature sensor in the combustion
chamber does not give a realistic temperature to
the stove control system.
Acknowledge error message and restart stove.
ERROR
FAN
DEFECT
The flue gas blower specified speed was not
reached.
Acknowledge error message and restart stove.
ERROR
CONVEYOR
JAMMED
The conveyor can not be controlled correctly.
Acknowledge error message and restart stove.