48
RIELLOTECH CLIMA TOP - CLIMA COMFORT
RIELLOTECH CLIMA TOP - CLIMA COMFORT
Operat-
ing line
User
level Function
Default value
Min
Max
Unit
5950
I
Function input H1
Optg mode changeover HCs +DHW ¦ Optg mode changeover DHW ¦
Optg mode changeover HCs ¦ Optg mode changeover HC1 ¦ Optg
mode changeover HC2 ¦ Optg mode change HC3 ¦ Error /alarm
message ¦ Cons request CC1 ¦ Cons request CC2 ¦ Release swim pool
source ¦ Release swim pool solar ¦ Operational level DHW ¦ Opera-
tional level HC1 ¦ Operational level HC2 ¦ Operational level HC3 ¦
Room thermostat HC1 ¦ Room thermostat HC2 ¦ Room thermostat
HC3 ¦ circ pump thermostat ¦ Pulse count ¦ Dewpoint monitor ¦
Flow temp setp incr hygro ¦ Boiler return thermostat ¦ Operational
signal supplementary source ¦ Flow measurement Hz ¦ Cons re-
quest CC1 10V ¦ Cons request CC2 10V ¦ Pressure measurement 10V ¦
Relative room humidity 10V ¦ Room temperature 10V ¦ Flow meas-
urement 10V ¦ Temperature measurement 10V.
Optg mode changeo-
ver HCs+DHW
-
-
-
5951
I
Contact type H1
NC ¦ NO
Make contact (NO)
-
-
-
5952 (***)
I
70
8
120
°C
5953 (**)
I
Input value 1 H1
0
0
1000
-
5954 (**)
I
Function value 1 H1
0
-100
500
-
5954 (***)
I
Temp value 10V H1
100
5
130
°C
5955 (**)
I
Input value 2 H1
10
0
1000
-
5956 (**)
I
Function value 2 H1
100
-100
500
-
5956 (***)
I
Pressure value 3.5V H1
5.0
0.0
10.0
bar
5957(**)
I
Temperature sensor H1
None ¦ Solar flow sensor B63 ¦ Solar return sensor B64
None
-
-
-
5960
I
Function input H3
Optg mode changeover HCs +DHW ¦ Optg mode changeover DHW ¦
Optg mode changeover HCs ¦ Optg mode changeover HC1 ¦ Optg
mode changeover HC2 ¦ Optg mode change HC3 ¦ Error /alarm
message ¦ Cons request CC1 ¦ Cons request CC2 ¦ Release swim pool
source ¦ Release swim pool solar ¦ Operational level DHW ¦ Opera-
tional level HC1 ¦ Operational level HC2 ¦ Operational level HC3 ¦
Room thermostat HC1 ¦ Room thermostat HC2 ¦ Room thermostat
HC3 ¦ circ pump thermostat ¦ Pulse count ¦ Dewpoint monitor ¦
Flow temp setp incr hygro ¦ Boiler return thermostat ¦ Operational
signal supplementary source ¦ Flow measurement Hz ¦ Cons re-
quest CC1 10V ¦ Cons request CC2 10V ¦ Pressure measurement 10V ¦
Relative room humidity 10V ¦ Room temperature 10V ¦ Flow meas-
urement 10V ¦ Temperature measurement 10V.
Optg mode changeo-
ver HCs+DHW
-
-
-
5961
I
Contact type H3
NC ¦ NO
Make contact (NO)
-
-
-
5962 (***)
I
Min flow temp setpoint H3
70
8
120
°C
5963(**)
I
Input value 1 H3
0
0
1000
-
5964
I
Function value 1 H3
0
-100
500
-
5965(**)
I
Input value 2 H3
10
0
1000
-
5966
I
Function value 2 H3
100
-100
500
-
5967(**)
I
Temperature sensor H3
None ¦ Solar flow sensor B63 ¦ Solar return sensor B64
None
-
-
-
5980(**)
F
Function input EX1
None ¦ Counter 1st burner stage ¦ Heat gen lock ¦ Error/alarm mes-
sage ¦ Excess heat discharge
Counter 1st burner
stage
-
-
-
5981(**)
F
Cont type input EX1
NC ¦ NO
Make contact (NO)
-
-
-
5982(***)
I
Function input EX2
Counter 2nd burner stage ¦ Heat generation lock ¦ Error/alarm
message ¦ SLT error message ¦ Excess heat discharge
Counter for second
burner stage
-
-
-
5983(***)
I
Cont type input EX2
NC ¦ NO
NO
-
-
-
5986(**)
F
SLT error message input L1
Off ¦ Always ¦ Automatically
Automatically
-
-
-
6014
I
Function mixing group 1
Multifunctional ¦ Heating circuit 1 ¦ Return controller ¦ Prim cntr/
system pump ¦ DHW primary controller ¦ Instantaneous DHW
heater ¦ Return temp controller cascade ¦ Cooling circuit ¦ Heating
circuit/Cooling circuit 1 ¦ Return controller solid fuel boiler.
Heating circuit 1
-
-
-
6015(***)
I
Function mixing group 2
Heating circuit 2 ¦ Return temp controller ¦ Prim contr/system
pump ¦ DHW primary controller ¦ Instantaneous DHW heater ¦
Return controller cascade
-
-
-
-
6097
F
Sensor type collector
NTC ¦ Pt 1000
NTC
-
-
-
6098
F
Readjustm collector sensor
0
-20
20
°C
6099
F
Readjustm coll sensor 2
0
-20
20
°C