45
RIELLOTECH CLIMA TOP - CLIMA COMFORT
RIELLOTECH CLIMA TOP - CLIMA COMFORT
Operat-
ing line
User
level Function
Default value
Min
Max
Unit
5090
F
With buffer
No ¦ Yes
No
-
-
-
5092
F
With prim contr/system pump
No ¦ Yes
No
-
-
-
5093
F
With solar integration
No ¦ Yes
Yes
-
-
-
5101
F
Pump speed min
40
0
100
%
5102
F
Pump speed max
100
0
100
%
5103(***)
O
speed Xp
32
1
100
%
5104(***)
O
speed Tn
120
10
873
%
5120
O
Mixing valve boost
0
0
50
°C
5124
F
Actuator running time
120
30
873
S
5125
O
Mixing valve Xp
24
1
100
°C
5126
O
Mixing valve Tn
90
10
873
S
5130
F
Transfer strategy
Off ¦ Always ¦ DHW release
Always
-
-
-
5131
F
Comparison temp transfer
With B3 ¦ With B31 ¦ With B3 and B31
With B3
-
-
-
5140(**)
F
Intermediate circuit boost
2
0
10
°C
5142(**)
O
Flow setp compensation delay
30
0
60
s
5143(**)
O
Flow setp compensation Xp
24
1
100
°C
5144(**)
O
Flow setp compensation Tn
120
10
873
s
5145(**)
O
Flow setp compensation Tv
0
0
60
s
5146(**)
F
Full charging with B36
No ¦ Yes
No
-
-
-
5148(**)
F
Min start temp diff Q33
-5
-20
20
°C
5149(**)
F
Start delay Q33
10
0
255
s
5160(**)
F
Legionella funct mixing pump
Off ¦ With charging ¦ With charging and duration
With charging and
duration
-
-
-
5165(**)
F
Restratification
Off ¦ On
Off
-
-
-
5166(**)
F
Restrat temp min
8
8
95
°C
5167(**)
F
Restrat temp diff min
8
0
40
°C
Instantaneous DHW heater
5406
F
Min setp diff to tank temp
4
0
20
°C
5420(**)
F
Flow setpoint boost
6
0
30
°C
5429(**)
O
Switching diff
1
0
20
°C
5455(**)
F
Setp readj cons 40°C
0
-20
20
°C
5456(**)
F
Setp readj cons 60°C
0
-20
20
°C
5460(**)
F
Setpoint keep hot
50
10
60
°C
5461(**)
F
Readj setp keep hot 40°C
4
-20
20
°C
5462(**)
F
Readj setp keep hot 60°C
4
-20
20
°C
5464(**)
F
Keep hot release
None ¦ 24h/day ¦ DHW release ¦ Time program 3/HC3 ¦ Time pro-
gram 4/DHW ¦ Time program 5
24h / day
-
-
-
5470(**)
F
Keep hot time wo heating
2
0
1440
min
5471(**)
F
Keep hot time with heating
0
0
30
min
5472(**)
F
Pump overrun time keep hot
0
0
255
min
5473(**)
F
Pump overrun time keep hot
20
0
59
s
5475(**)
F
Control sensor keep hot
Boiler sensor B2 ¦ Return sensor B7 ¦ DHW outlet sensor B38
Boiler sensor B2
-
-
-
5476(**)
F
Keep hot periodically
1
1
255
Min
5477(**)
F
Min keep hot time
0
0
255
s
5478(**)
F
Keep hot in heating mode
Off ¦ On
Off
-
-
-
5489(**)
F
Overrun via inst WH
No ¦ Yes
No
-
-
-
5544
F
Actuator running time
15
7,5
480
s
5545
O
Mixing valve Xp
20
1
200
°C
5546
O
Mixing valve Tn
150
10
873
s
5547
O
Mixing valve Tv
4,5
0
30
s