Operat-
ing line
User
level Function
Default value
Min
Max
Unit
4726(**)
O
Max st tank temp cool mode
25
- - - / 10
40
°C
4728(**)
F
Rel temp diff buffer/HC
0
-50
50
%
4739(**)
F
Stratification protection
Off ¦ Always ¦ With solid fuel boiler
Off
-
-
-
4740(**)
O
Strat prot temp diff max
5
0
20
°C
4743(**)
O
Strat prot anticipation time
60
0
240
s
4744(**)
O
Strat protection Tn
120
10
200
s
4746(**)
O
DHW prot combi st tank
Off ¦ On
Off
-
-
-
4749(**)
F
Min charging setpoint solar
8
8
94
°C
4750
F
Charging temp max
80
8
95
°C
4751
O
Storage tank temp max
90
8
95
°C
4755
F
Recooling temp
70
8
95
°C
4756
F
Recooling DHW/HCs
Off ¦ On
Off
-
-
-
4757
F
Recooling collector
Off ¦ Summer ¦ Always
Off
-
-
-
4783
F
With solar integration
No ¦ Yes
No
-
-
-
4790
F
Temp diff on return div
10
0
40
°C
4791
F
Temp diff off return div
5
0
40
°C
4795
F
Compar temp return div
B4 ¦ B41 ¦ B42
B42
-
-
-
4796
F
Optg action return diversion
Temp decrease ¦ Temp increase
Temp Increase
-
-
-
4800
F
Partial charging setpoint
- - -
- - - / 8
95
°C
4810
F
Full charging
Off ¦ Current heat request ¦ Buffer setpoint
Buffer setpoint
-
-
-
4811
F
Full charge temperature min.
8
8
80
°C
4813
F
Full charging
With B4 ¦ With B42/B41
With B42/B41
-
-
-
DHW storage tank
5010
O
Charging
Once/day ¦ Several times/day
Several times/day
-
-
-
5020
F
Flow setpoint boost
16
0
30
°C
5021
F
Transfer boost
8
0
30
°C
5022
F
Type of charging
Recharging ¦ Full charging ¦ Full charging legio ¦ Full charg 1st time
day ¦ Full charg 1st time legio
Full charge
-
-
-
5024
O
Switching diff
3
0
20
°C
5030
O
Charging time limitation
- - -
- - - / 10
600
min
5040
O
Discharging protection
Off ¦ Always ¦ Automatically
Automatically
-
-
-
5050
F
Charging temp max
80
8
OL 5051
OEM
°C
5051
O
Storage tank temp max
80
8
95
°C
5055
F
Recooling temp
70
8
95
°C
5056
F
Recooling heat gen/HCs
Off ¦ On
Off
-
-
-
5057
F
Recooling collector
Off ¦ Summer ¦ Always
Off
-
-
-
5060
F
El imm heater optg mode
Substitute ¦ Summer ¦ Always
Substitute
-
-
-
5061
F
El immersion heater release
24h/day ¦ DHW release ¦ Time program 4/DHW
DHW release
-
-
-
5062
F
El immersion heater control
External thermostat ¦ DHW sensor
DHW sensor
-
-
-
5063(**)
F
El immersion heater control For Eco mode
On ¦ Off
On
-
-
-
5070
O
Automatic push
Off ¦ On
On
-
-
-
5071
O
Charging prio time push
0
0
120
min
5085
F
Excess heat draw
Off ¦ On
On
-
-
-